1DELL-SNMP-UPS-MIB DEFINITIONS ::= BEGIN
2
3-- Title:       UPS MIB
4-- Date:        August 8th, 2013
5-- Author:      Eaton - R&D Communication
6-- Release:     01.04.0002
7-- NMC Firmware compatibility:     01.18.000x
8
9IMPORTS
10        enterprises
11                FROM RFC1155-SMI
12        TimeStamp, DisplayString
13                FROM SNMPv2-TC
14        OBJECT-TYPE
15                FROM RFC-1212
16        TRAP-TYPE
17                FROM RFC-1215;
18
19----
20-- Path to the root
21----
22dell        OBJECT IDENTIFIER ::= { enterprises 674 }
23upsdell     OBJECT IDENTIFIER ::= { dell 10902 }
24hardware    OBJECT IDENTIFIER ::= { upsdell 2 }
25
26
27
28-- Groups of the MIB
29productID       OBJECT IDENTIFIER ::= { hardware 100 }
30productStatus   OBJECT IDENTIFIER ::= { hardware 110 }
31physical        OBJECT IDENTIFIER ::= { hardware 120 }
32logical         OBJECT IDENTIFIER ::= { hardware 130 }
33traps           OBJECT IDENTIFIER ::= { hardware 140 }
34
35-- Groups of the Physical group
36physicalIdent       OBJECT IDENTIFIER ::= { physical 1 }
37physicalOutput      OBJECT IDENTIFIER ::= { physical 2 }
38physicalRectifier   OBJECT IDENTIFIER ::= { physical 3 }
39physicalUPS         OBJECT IDENTIFIER ::= { physical 4 }
40physicalBattery     OBJECT IDENTIFIER ::= { physical 5 }
41physicalLoadSegment OBJECT IDENTIFIER ::= { physical 6 }
42physicalEnvironment OBJECT IDENTIFIER ::= { physical 7 }
43
44----
45-- Definition of object types
46----
47
48--------------------------
49-- the productID group --
50--------------------------
51
52productIDDisplayName OBJECT-TYPE
53        SYNTAX DisplayString
54        ACCESS read-only
55        STATUS mandatory
56        DESCRIPTION
57                "Name of this product for display purposes."
58        ::= { productID 1 }
59
60productIDDescription OBJECT-TYPE
61        SYNTAX DisplayString(SIZE(0..32))
62        ACCESS read-only
63        STATUS mandatory
64        DESCRIPTION
65                "A short description of this product."
66        ::= { productID 2 }
67
68productIDVendor OBJECT-TYPE
69        SYNTAX DisplayString(SIZE(0..32))
70        ACCESS read-only
71        STATUS mandatory
72        DESCRIPTION
73                "The name of the product manufacturer."
74        ::= { productID 3 }
75
76productIDVersion OBJECT-TYPE
77        SYNTAX DisplayString(SIZE(0..32))
78        ACCESS read-only
79        STATUS mandatory
80        DESCRIPTION
81                "The version of this product."
82        ::= { productID 4 }
83
84productIDBuildNumber OBJECT-TYPE
85        SYNTAX DisplayString(SIZE(0..32))
86        ACCESS read-only
87        STATUS mandatory
88        DESCRIPTION
89                "The software build number of the product populating the MIB."
90        ::= { productID 5 }
91
92productIDURL OBJECT-TYPE
93        SYNTAX DisplayString(SIZE(0..32))
94        ACCESS read-only
95        STATUS mandatory
96        DESCRIPTION
97                "The URL of the web-based application to manage this device, should the device provide one."
98        ::= { productID 6 }
99
100productIDDeviceNetworkName OBJECT-TYPE
101        SYNTAX DisplayString(SIZE(0..32))
102        ACCESS read-only
103        STATUS mandatory
104        DESCRIPTION
105                "Operating system specific computer name if product SNMP service is hosted."
106        ::= { productID 7 }
107
108--------------------------
109-- the productStatus group --
110--------------------------
111
112productStatusGlobalStatus OBJECT-TYPE
113        SYNTAX INTEGER {
114                other(1),
115                unknown(2),
116                ok(3),
117                non-critical(4),
118                critical(5),
119                non-recoverable(6)
120        }
121        ACCESS read-only
122        STATUS mandatory
123        DESCRIPTION
124                "Current status of the product.
125                This is a rollup for the entire product including any
126                monitored devices. The status is intended to give
127                initiative to an SNMP monitor to get further data when
128                this status is abnormal."
129        ::= { productStatus 1 }
130
131productStatusLastGlobalStatus OBJECT-TYPE
132        SYNTAX INTEGER
133        ACCESS read-only
134        STATUS mandatory
135        DESCRIPTION
136                "The status before the current status which induced an initiative
137                to issue a global status change trap."
138        ::= { productStatus 2 }
139
140productStatusTimeStamp OBJECT-TYPE
141        SYNTAX TimeStamp
142        ACCESS read-only
143        STATUS mandatory
144        DESCRIPTION
145                "The last time that the SNMP table geometries changed and/or
146                attribute data was significantly updated.  This is to be used by
147                management applications to trigger a refresh of data acquired
148                from the MIB."
149        ::= { productStatus 3 }
150
151productStatusGetTimeOut OBJECT-TYPE
152        SYNTAX INTEGER
153        ACCESS read-only
154        STATUS optional
155        DESCRIPTION
156                "Suggested time out value in milliseconds for how long the SNMP getter
157                should wait while attempting to poll the product SNMP service."
158        ::= { productStatus 4 }
159
160productStatusRefreshRate OBJECT-TYPE
161        SYNTAX INTEGER
162
163        ACCESS read-only
164        STATUS optional
165        DESCRIPTION
166                "Rate in seconds at which the SNMP service cached data is being updated."
167        ::= { productStatus 5 }
168
169productStatusGeneratingTrapFlag OBJECT-TYPE
170        SYNTAX INTEGER {
171                true(1),
172                false(2),
173                disabled(3)
174        }
175        ACCESS read-only
176        STATUS optional
177        DESCRIPTION
178                "Indicates if this SNMP sub-agent is capable of and/or is generating SNMP Traps.
179                This variable can take the following values:
180                1 True, this service is capable of sending traps and is the originator of SNMP
181                  traps generated for the devices represented in this MIB and is currently generating traps.
182                2 False, this service not capable of sending traps and is not the originator of
183                  any SNMP traps generated for the devices represented in this MIB.
184                3 Disabled, this service is capable of sending traps and is the originator of SNMP
185                  traps for the devices represented in this MIB, but traps are currently disabled."
186        ::= { productStatus 6 }
187
188--------------------------
189-- the Physical group --
190--------------------------
191
192-- physicalIdent group
193
194physicalIdentFamilyName OBJECT-TYPE
195        SYNTAX DisplayString(SIZE(0..32))
196        ACCESS read-only
197        STATUS mandatory
198        DESCRIPTION
199                "UPS Family name."
200        ::= { physicalIdent 1 }
201
202physicalIdentSerialNumber OBJECT-TYPE
203        SYNTAX DisplayString(SIZE(0..32))
204        ACCESS read-only
205        STATUS mandatory
206        DESCRIPTION
207                "UPS Serial number."
208        ::= { physicalIdent 2 }
209
210physicalIdentConverterType OBJECT-TYPE
211        SYNTAX INTEGER {
212                lineInteractive(1),
213                onLine(2),
214                onLineUnitaryParallel(3),
215                onLineParallelWithNS(4),
216                onLineHotStandbyRedundancy(5)
217        }
218        ACCESS read-only
219        STATUS mandatory
220        DESCRIPTION
221                "UPS type."
222        ::= { physicalIdent 3 }
223
224physicalIdentReferenceNumber OBJECT-TYPE
225        SYNTAX DisplayString(SIZE(0..32))
226        ACCESS read-only
227        STATUS mandatory
228        DESCRIPTION
229                "Technical Reference of UPS firmware."
230        ::= { physicalIdent 4 }
231
232-- physicalOutput group
233
234physicalOutputInstantHeadroom OBJECT-TYPE
235        SYNTAX INTEGER
236        ACCESS read-only
237        STATUS mandatory
238        DESCRIPTION
239                "This is the present amount of watt capacity remaining before overload."
240        ::= { physicalOutput 1 }
241
242physicalOutputPeakHeadroom OBJECT-TYPE
243        SYNTAX INTEGER
244        ACCESS read-only
245        STATUS mandatory
246        DESCRIPTION
247                "Statistical value holding the lowest value that Instantaneous Headroom
248                Watts was ever set too since the last time this statistic was reset."
249        ::= { physicalOutput 2 }
250
251physicalOutputPeakHeadroomTimestamp OBJECT-TYPE
252        SYNTAX TimeStamp
253        ACCESS read-only
254        STATUS mandatory
255        DESCRIPTION
256                "Time and date stamp of the last time the Peak Headroom Watts value was updated."
257        ::= { physicalOutput 3 }
258
259physicalOutputPeakConsumption OBJECT-TYPE
260        SYNTAX INTEGER
261        ACCESS read-only
262        STATUS mandatory
263        DESCRIPTION
264                "Statistical value of the maximum RMS Watts the UPS has seen since
265                the last time this statistic was reset."
266        ::= { physicalOutput 4 }
267
268physicalOutputPeakConsumptionTimestamp OBJECT-TYPE
269        SYNTAX TimeStamp
270        ACCESS read-only
271        STATUS mandatory
272        DESCRIPTION
273                "Time and date stamp of the last time the Peak Consumption Watts value was updated."
274        ::= { physicalOutput 5 }
275
276physicalOutputPresentConsumption OBJECT-TYPE
277        SYNTAX INTEGER
278        ACCESS read-only
279        STATUS mandatory
280        DESCRIPTION
281                "Derived by averaging the watt second consumption over the past hour.
282                Use an array of 60 words to store the average watt seconds consumed over
283                the last minute then after you have a full hours worth of data in the 60
284                word array, average those values to get your Present KWH Consumption meter.
285                Then every minute after that update the oldest value in the array, average
286                again and update the meter.
287                Value is 0 until the minimum 1 hour of data has been accumulated."
288        ::= { physicalOutput 6 }
289
290physicalOutputCumulativeConsumption OBJECT-TYPE
291        SYNTAX INTEGER
292        ACCESS read-only
293        STATUS mandatory
294        DESCRIPTION
295                "64 bit meter value that is derived by reading the Present KWH Consumption meter
296                once per hour and adding it to the last value of this meter. Value accumulates
297                until it is reset from the LCD or via the SHUT protocol or the meter rolls over."
298        ::= { physicalOutput 7 }
299
300physicalOutputCumulativeConsumptionTimestamp OBJECT-TYPE
301        SYNTAX TimeStamp
302        ACCESS read-only
303        STATUS mandatory
304        DESCRIPTION
305                "Time and date stamp of last time this meter value was reset."
306        ::= { physicalOutput 8 }
307
308physicalOutputVA OBJECT-TYPE
309        SYNTAX INTEGER
310        ACCESS read-only
311        STATUS mandatory
312        DESCRIPTION
313                "Output VA."
314        ::= { physicalOutput 9 }
315
316
317-- physicalRectifier group
318
319physicalRectifierPosVoltage OBJECT-TYPE
320        SYNTAX INTEGER
321        ACCESS read-only
322        STATUS mandatory
323        DESCRIPTION
324                "DC bus positive voltage."
325        ::= { physicalRectifier 1 }
326
327physicalRectifierNegVoltage OBJECT-TYPE
328        SYNTAX INTEGER
329        ACCESS read-only
330        STATUS mandatory
331        DESCRIPTION
332                "DC bus negative  voltage."
333        ::= { physicalRectifier 2 }
334
335
336-- physicalUPS group
337
338physicalUPSDateTime OBJECT-TYPE
339        SYNTAX TimeStamp
340        ACCESS read-only
341        STATUS mandatory
342        DESCRIPTION
343                "Real Time Clock with Date and Time."
344        ::= { physicalUPS 1 }
345
346physicalUPSAlarmsStatus OBJECT-TYPE
347        SYNTAX DisplayString
348        ACCESS read-only
349        STATUS mandatory
350        DESCRIPTION
351                "List of traps that are in active mode. This list is coded in ASCI format
352                and each trap number is separated by a coma (ex: 1,5,23,77). Only odd traps
353                are listed."
354        ::= { physicalUPS 2 }
355
356physicalUPSRuntimeToShutdown OBJECT-TYPE
357        SYNTAX INTEGER
358        ACCESS read-only
359        STATUS mandatory
360        DESCRIPTION
361                "Number of seconds remaining until UPS will receive a ShutdownAfterDelay command.
362                2147483647 if no countdown is in effect."
363        ::= { physicalUPS 3 }
364
365physicalUPSOutpoutSwitchable OBJECT-TYPE
366        SYNTAX INTEGER {
367                switchable(1),
368                notSwitchable(2)
369        }
370        ACCESS read-only
371        STATUS mandatory
372        DESCRIPTION
373                "Parameter to enable or not remote UPS commands coming from all communication ports."
374        ::= { physicalUPS 4 }
375
376
377-- physicalBattery group
378
379physicalBatteryABMStatus OBJECT-TYPE
380        SYNTAX INTEGER {
381                abmCharging(1),
382                abmDischarging(2),
383                abmFloating(3),
384                abmResting(4),
385                abmOff(5)
386        }
387        ACCESS read-only
388        STATUS mandatory
389        DESCRIPTION
390                "Advanced Battery Monitoring satus."
391        ::= { physicalBattery 1 }
392
393physicalBatteryTestStatus OBJECT-TYPE
394        SYNTAX INTEGER {
395                donePassed(1),
396                doneWarning(2),
397                doneError(3),
398                aborted(4),
399                inProgress(5),
400                noTestIniated(6),
401                testScheduled(7)
402        }
403        ACCESS read-only
404        STATUS mandatory
405        DESCRIPTION
406                "Battery test satus."
407        ::= { physicalBattery 2 }
408
409physicalBatterySecondsRemaining OBJECT-TYPE
410        SYNTAX INTEGER
411        ACCESS read-only
412        STATUS mandatory
413        DESCRIPTION
414                "Battery remaining time calculated by the autonometer."
415        ::= { physicalBattery 3 }
416
417
418-- physicalLoadSegment group
419
420physicalLoadSegment1ShutdownAfterDelay OBJECT-TYPE
421        SYNTAX INTEGER
422        ACCESS read-only
423        STATUS mandatory
424        DESCRIPTION
425                "Number of seconds remaining until load segment 1 will switch off.
426                 -1 if no shutdown countdown is in effect."
427        ::= { physicalLoadSegment 1 }
428
429physicalLoadSegment1StartupAfterDelay OBJECT-TYPE
430        SYNTAX INTEGER
431        ACCESS read-only
432        STATUS mandatory
433        DESCRIPTION
434                "Number of seconds remaining until load segment 1 will switch on.
435                 -1 if no startup countdown is in effect."
436        ::= { physicalLoadSegment 2 }
437
438physicalLoadSegment2ShutdownAfterDelay OBJECT-TYPE
439        SYNTAX INTEGER
440        ACCESS read-only
441        STATUS mandatory
442        DESCRIPTION
443                "Number of seconds remaining until load segment 2 will switch off.
444                 -1 if no shutdown countdown is in effect."
445        ::= { physicalLoadSegment 3 }
446
447physicalLoadSegment2StartupAfterDelay OBJECT-TYPE
448        SYNTAX INTEGER
449        ACCESS read-only
450        STATUS mandatory
451        DESCRIPTION
452                "Number of seconds remaining until load segment 2 will switch on.
453                 -1 if no startup countdown is in effect."
454        ::= { physicalLoadSegment 4 }
455
456physicalLoadSegment1RuntimeToShutdown OBJECT-TYPE
457        SYNTAX INTEGER
458        ACCESS read-only
459        STATUS mandatory
460        DESCRIPTION
461                "Number of seconds remaining until load segment 1 will receive a
462                ShutdownAfterDelay command. 2147483647 if no countdown is in effect."
463        ::= { physicalLoadSegment 5 }
464
465physicalLoadSegment2RuntimeToShutdown OBJECT-TYPE
466        SYNTAX INTEGER
467        ACCESS read-only
468        STATUS mandatory
469        DESCRIPTION
470                "Number of seconds remaining until load segment 2 will receive a
471                ShutdownAfterDelay command. 2147483647 if no countdown is in effect."
472        ::= { physicalLoadSegment 6 }
473
474-- physicalEnvironment group
475
476physicalEnvironmentSensorPresent OBJECT-TYPE
477        SYNTAX INTEGER
478        ACCESS read-only
479        STATUS mandatory
480        DESCRIPTION
481                "Informations, if there is Environment Measurement Probe connected."
482        ::= { physicalEnvironment 1 }
483
484physicalEnvironmentSensorName OBJECT-TYPE
485        SYNTAX DisplayString(SIZE(0..59))
486        ACCESS read-only
487        STATUS mandatory
488        DESCRIPTION
489                "User name of EMP."
490        ::= { physicalEnvironment 2 }
491
492physicalEnvironmentValues OBJECT IDENTIFIER ::= { physicalEnvironment 3 }
493
494physicalEnvironmentValuesTemperatureUnit OBJECT-TYPE
495        SYNTAX INTEGER {
496                celsius(1),
497                fahrenheit(2)
498        }
499        ACCESS read-only
500        STATUS mandatory
501        DESCRIPTION
502                "Temperature unit setting."
503        ::= { physicalEnvironmentValues 1 }
504
505physicalEnvironmentValuesTemperature OBJECT-TYPE
506        SYNTAX INTEGER
507        ACCESS read-only
508        STATUS mandatory
509        DESCRIPTION
510                "Current temperature value in 0.1 degree Celsius."
511        ::= { physicalEnvironmentValues 2 }
512
513physicalEnvironmentValuesHumidity OBJECT-TYPE
514        SYNTAX INTEGER
515        ACCESS read-only
516        STATUS mandatory
517        DESCRIPTION
518                "Current humidity value in 0.1 percents."
519        ::= { physicalEnvironmentValues 3 }
520
521physicalEnvironmentValuesTemperatureLow OBJECT-TYPE
522        SYNTAX INTEGER
523        ACCESS read-only
524        STATUS mandatory
525        DESCRIPTION
526                "Temperature low threshhold in units of degree Celsius."
527        ::= { physicalEnvironmentValues 4 }
528
529physicalEnvironmentValuesTemperatureHigh OBJECT-TYPE
530        SYNTAX INTEGER
531        ACCESS read-only
532        STATUS mandatory
533        DESCRIPTION
534                "Temperature high threshhold in units of degree Celsius."
535        ::= { physicalEnvironmentValues 5 }
536
537physicalEnvironmentValuesTemperatureHysteresis OBJECT-TYPE
538        SYNTAX INTEGER
539        ACCESS read-only
540        STATUS mandatory
541        DESCRIPTION
542                "Temperature hysteresis in units of degree Celsius."
543        ::= { physicalEnvironmentValues 6 }
544
545physicalEnvironmentValueshHumidityLow OBJECT-TYPE
546        SYNTAX INTEGER
547        ACCESS read-only
548        STATUS mandatory
549        DESCRIPTION
550                "Humidity low threshhold in percents."
551        ::= { physicalEnvironmentValues 7 }
552
553physicalEnvironmentValuesHumidityHigh OBJECT-TYPE
554        SYNTAX INTEGER
555        ACCESS read-only
556        STATUS mandatory
557        DESCRIPTION
558                "Humidity high threshhold in percents."
559        ::= { physicalEnvironmentValues 8 }
560
561physicalEnvironmentValuesHumidityHysteresis OBJECT-TYPE
562        SYNTAX INTEGER
563        ACCESS read-only
564        STATUS mandatory
565        DESCRIPTION
566                "Humidity hysteresis in percents."
567        ::= { physicalEnvironmentValues 9 }
568
569physicalEnvironmentInputTable OBJECT-TYPE
570        SYNTAX SEQUENCE OF PhysicalEnvironmentInputEntry
571        ACCESS not-accessible
572        STATUS mandatory
573        DESCRIPTION
574                "The table containins dry contact inputs information."
575        ::= { physicalEnvironment 4 }
576
577physicalEnvironmentInputEntry OBJECT-TYPE
578        SYNTAX PhysicalEnvironmentInputEntry
579        ACCESS not-accessible
580        STATUS mandatory
581        DESCRIPTION
582                "The description of an entry in the table."
583        INDEX   { physicalEnvironmentInputIndex }
584        ::= { physicalEnvironmentInputTable 1 }
585
586
587PhysicalEnvironmentInputEntry ::= SEQUENCE { -- ASN.1 type definition
588        physicalEnvironmentInputIndex INTEGER,
589        physicalEnvironmentInputName DisplayString,
590        physicalEnvironmentInputState INTEGER,
591        physicalEnvironmentInputOpenedState DisplayString,
592        physicalEnvironmentInputClosedState DisplayString
593        }
594
595physicalEnvironmentInputIndex OBJECT-TYPE
596        SYNTAX INTEGER (0..1)
597        ACCESS read-only
598        STATUS mandatory
599        DESCRIPTION
600                "The input index, ranging from 1 to 2."
601        ::= { physicalEnvironmentInputEntry 1 }
602
603physicalEnvironmentInputName OBJECT-TYPE
604        SYNTAX DisplayString(SIZE(0..27))
605        ACCESS read-only
606        STATUS mandatory
607        DESCRIPTION
608                "The input user-friendly name."
609        ::= { physicalEnvironmentInputEntry 2 }
610
611physicalEnvironmentInputState OBJECT-TYPE
612        SYNTAX INTEGER {
613                opened(1),
614                closed(2)
615        }
616        ACCESS read-only
617        STATUS mandatory
618        DESCRIPTION
619                "Current state of input."
620        ::= { physicalEnvironmentInputEntry 3 }
621
622physicalEnvironmentInputOpenedState OBJECT-TYPE
623        SYNTAX DisplayString(SIZE(0..21))
624        ACCESS read-only
625        STATUS mandatory
626        DESCRIPTION
627                "The input opened state user-friendly name."
628        ::= { physicalEnvironmentInputEntry 4 }
629
630physicalEnvironmentInputClosedState OBJECT-TYPE
631        SYNTAX DisplayString(SIZE(0..21))
632        ACCESS read-only
633        STATUS mandatory
634        DESCRIPTION
635                "The input closed state user-friendly name."
636        ::= { physicalEnvironmentInputEntry 5 }
637
638
639--------------------------
640-- the Logical group --
641--------------------------
642
643
644--------------------------
645-- the Traps group --
646--------------------------
647
648-- This group defines objects and traps, so that for each trap, simple
649-- get request on related objects (one or many) allow to confirm actual
650-- status of the trap.
651
652-- TRAPS NOTIFICATIONS
653
654trapInverterOverVoltage TRAP-TYPE
655        ENTERPRISE traps
656        DESCRIPTION
657                "Inverter AC over voltage."
658        --#SEVERITY WARNING
659        --#SUMMARY "The Inverter AC Voltage has exceeded the 'Over Voltage Threshold' value."
660::= 1
661
662trapInverterOverVoltageOk TRAP-TYPE
663        ENTERPRISE traps
664        DESCRIPTION
665                "Inverter AC over voltage ok."
666        --#SEVERITY INFORMATIONAL
667        --#SUMMARY "The Inverter AC Voltage is no longer over the 'Over Voltage Threshold' value."
668::= 2
669
670trapInverterUnderVoltage TRAP-TYPE
671        ENTERPRISE traps
672        DESCRIPTION
673                "Inverter AC under voltage."
674        --#SEVERITY WARNING
675        --#SUMMARY "Inverter AC Voltage has fallen below the 'Under Voltage Threshold' value."
676::= 3
677
678trapInverterUnderVoltageOk TRAP-TYPE
679        ENTERPRISE traps
680        DESCRIPTION
681                "Inverter AC under voltage ok."
682        --#SEVERITY INFORMATIONAL
683        --#SUMMARY "Inverter AC Voltage is no longer below the 'Under Voltage Threshold' value."
684::= 4
685
686trapBypassFrequencyOutOfRange TRAP-TYPE
687        ENTERPRISE traps
688        DESCRIPTION
689                "Bypass under or over frequency."
690        --#SEVERITY WARNING
691        --#SUMMARY "UPS Bypass Frequency has gone out of Range."
692::= 5
693
694trapBypassFrequencyOutOfRangeOk TRAP-TYPE
695        ENTERPRISE traps
696        DESCRIPTION
697                "Bypass under or over frequency ok."
698        --#SEVERITY INFORMATIONAL
699        --#SUMMARY "UPS Bypass Frequency is no longer out of Range."
700::= 6
701
702trapOnBuck TRAP-TYPE
703        ENTERPRISE traps
704        DESCRIPTION
705                "On Buck / Input Voltage Reducer."
706        --#SEVERITY INFORMATIONAL
707        --#SUMMARY "On Buck / Input Voltage Reducer."
708::= 7
709
710trapReturnFromBuck TRAP-TYPE
711        ENTERPRISE traps
712        DESCRIPTION
713                "Return from Buck."
714        --#SEVERITY INFORMATIONAL
715        --#SUMMARY "The UPS has returned from Buck."
716::= 8
717
718trapOnBoost TRAP-TYPE
719        ENTERPRISE traps
720        DESCRIPTION
721                "On Boost / Input Voltage Booster."
722        --#SEVERITY INFORMATIONAL
723        --#SUMMARY "On Boost / Input Voltage Booster."
724::= 9
725
726trapReturnFromBoost TRAP-TYPE
727        ENTERPRISE traps
728        DESCRIPTION
729                "Return from Boost."
730        --#SEVERITY INFORMATIONAL
731        --#SUMMARY "The UPS has returned from Boost."
732::= 10
733
734trapInputOverVoltage TRAP-TYPE
735        ENTERPRISE traps
736        DESCRIPTION
737                "Input AC over voltage."
738        --#SEVERITY WARNING
739        --#SUMMARY "Input AC Voltage to the UPS has exceeded the 'Over Voltage Threshold' value."
740::= 11
741
742trapInputOverVoltageOk TRAP-TYPE
743        ENTERPRISE traps
744        DESCRIPTION
745                "Input AC over voltage ok."
746        --#SEVERITY INFORMATIONAL
747        --#SUMMARY "Input AC Voltage to the UPS no longer above the 'Over Voltage Threshold' value."
748::= 12
749
750trapInputUnderVoltage TRAP-TYPE
751        ENTERPRISE traps
752        DESCRIPTION
753                "Input AC under voltage."
754        --#SEVERITY WARNING
755        --#SUMMARY "Input AC Voltage to the UPS has fallen below 'Input Low Voltage Threshold' value."
756::= 13
757
758trapInputUnderVoltageOk TRAP-TYPE
759        ENTERPRISE traps
760        DESCRIPTION
761                "Input AC under voltage ok."
762        --#SEVERITY INFORMATIONAL
763        --#SUMMARY "Input AC Voltage to the UPS is no longer below the 'Under Voltage Threshold' value."
764::= 14
765
766trapInputFrequencyOutOfRange TRAP-TYPE
767        ENTERPRISE traps
768        DESCRIPTION
769                "Input under or over frequency."
770        --#SEVERITY WARNING
771        --#SUMMARY "Input Frequency to UPS has fallen out of Range."
772::= 15
773
774trapInputFrequencyOutOfRangeOk TRAP-TYPE
775        ENTERPRISE traps
776        DESCRIPTION
777                "Input under or over frequency ok."
778        --#SEVERITY INFORMATIONAL
779        --#SUMMARY "Input Frequency to UPS is no longer out of Range."
780::= 16
781
782trapRemoteEmergencyPowerOff TRAP-TYPE
783        ENTERPRISE traps
784        DESCRIPTION
785                "Remote emergency power off."
786        --#SEVERITY WARNING
787        --#SUMMARY "Remote emergency power off."
788::= 17
789
790trapReturnFromEmergencyPowerOff TRAP-TYPE
791        ENTERPRISE traps
792        DESCRIPTION
793                "Return from remote emergency power off."
794        --#SEVERITY INFORMATIONAL
795        --#SUMMARY "Return from remote emergency power off."
796::= 18
797
798trapLevel1Overload TRAP-TYPE
799        ENTERPRISE traps
800        DESCRIPTION
801                "Output Level 1 overload."
802        --#SEVERITY WARNING
803        --#SUMMARY "UPS Output has exceeded the 'OverLoad Level 1 Threshold' value."
804::= 19
805
806trapLevel1OverloadOk TRAP-TYPE
807        ENTERPRISE traps
808        DESCRIPTION
809                "Output Level 1 overload ok."
810        --#SEVERITY INFORMATIONAL
811        --#SUMMARY "UPS Output is no longer above the 'Overload Level 1 threshold' value."
812::= 20
813
814trapLevel2Overload TRAP-TYPE
815        ENTERPRISE traps
816        DESCRIPTION
817                "Level 2 overload."
818        --#SEVERITY WARNING
819        --#SUMMARY "UPS Output has exceeded the 'OverLoad Level 2 Threshold' value."
820::= 21
821
822trapLevel2OverloadOk TRAP-TYPE
823        ENTERPRISE traps
824        DESCRIPTION
825                "Level 2 overload ok."
826        --#SEVERITY INFORMATIONAL
827        --#SUMMARY "UPS Output is no longer above the 'Overload Level 2 threshold' value."
828::= 22
829
830trapLevel3Overload TRAP-TYPE
831        ENTERPRISE traps
832        DESCRIPTION
833                "Level 3 overload."
834        --#SEVERITY CRITICAL
835        --#SUMMARY "UPS Output has exceeded the 'OverLoad Level 3 Threshold' value."
836::= 23
837
838trapLevel3OverloadOk TRAP-TYPE
839        ENTERPRISE traps
840        DESCRIPTION
841                "Level 3 overload ok."
842        --#SEVERITY INFORMATIONAL
843        --#SUMMARY "UPS Output is no longer above the 'Overload Level 3 threshold' value."
844::= 24
845
846trapPosDCLinkOverVoltage TRAP-TYPE
847        ENTERPRISE traps
848        DESCRIPTION
849                "Positive DC link over voltage."
850        --#SEVERITY WARNING
851        --#SUMMARY "Positive DC link voltage has exceeded the 'Over Voltage Threshold' value."
852::= 25
853
854trapPosDCLinkOverVoltageOk TRAP-TYPE
855        ENTERPRISE traps
856        DESCRIPTION
857                "Positive DC link over voltage ok."
858        --#SEVERITY INFORMATIONAL
859        --#SUMMARY "Positive DC link Voltage is no longer above the "Over Voltage Threshold" value."
860::= 26
861
862trapPosDCLinkUnderVoltage TRAP-TYPE
863        ENTERPRISE traps
864        DESCRIPTION
865                "Positive DC link under voltage."
866        --#SEVERITY WARNING
867        --#SUMMARY "Positive DC Link Voltage has fallen below 'Low Voltage Threshold' value."
868::= 27
869
870trapPosDCLinkUnderVoltageOk TRAP-TYPE
871        ENTERPRISE traps
872        DESCRIPTION
873                "Positive DC link under voltage ok."
874        --#SEVERITY INFORMATIONAL
875        --#SUMMARY "Positive DC link Voltage is no longer below the 'Under Voltage Threshold' value."
876::= 28
877
878trapNegDCLinkOverVoltage TRAP-TYPE
879        ENTERPRISE traps
880        DESCRIPTION
881                "Negative DC link over voltage."
882        --#SEVERITY WARNING
883        --#SUMMARY "Negative DC link Voltage has exceeded the 'Over Voltage Threshold' value."
884::= 29
885
886trapNegDCLinkOverVoltageOk TRAP-TYPE
887        ENTERPRISE traps
888        DESCRIPTION
889                "Negative DC link over voltage ok."
890        --#SEVERITY INFORMATIONAL
891        --#SUMMARY "Negative DC link over voltage is no longer above the 'Over Voltage Threshold' value."
892::= 30
893
894trapNegDCLinkUnderVoltage TRAP-TYPE
895        ENTERPRISE traps
896        DESCRIPTION
897                "Negative DC link under voltage."
898        --#SEVERITY WARNING
899        --#SUMMARY "Negative DC link Voltage has fallen below 'Low Voltage Threshold' value."
900::= 31
901
902trapNegDCLinkUnderVoltageOk TRAP-TYPE
903        ENTERPRISE traps
904        DESCRIPTION
905                "Negative DC link under voltage ok."
906        --#SEVERITY INFORMATIONAL
907        --#SUMMARY "Negative DC link Voltage is no longer below the 'Under Voltage Threshold' value."
908::= 32
909
910trapRectifierFault TRAP-TYPE
911        ENTERPRISE traps
912        DESCRIPTION
913                "Rectifier fault."
914        --#SEVERITY CRITICAL
915        --#SUMMARY "Rectifier fault has occured."
916::= 33
917
918trapRectifierOk TRAP-TYPE
919        ENTERPRISE traps
920        DESCRIPTION
921                "Rectifier ok."
922        --#SEVERITY INFORMATIONAL
923        --#SUMMARY "Rectifier is functioning normally."
924::= 34
925
926trapInverterFault TRAP-TYPE
927        ENTERPRISE traps
928        DESCRIPTION
929                "Inverter fault."
930        --#SEVERITY CRITICAL
931        --#SUMMARY "There is an Inverter fault."
932::= 35
933
934trapInverterOk TRAP-TYPE
935        ENTERPRISE traps
936        DESCRIPTION
937                "Inverter ok."
938        --#SEVERITY INFORMATIONAL
939        --#SUMMARY "Inverter is functioning normally."
940::= 36
941
942trapChargerFailure TRAP-TYPE
943        ENTERPRISE traps
944        DESCRIPTION
945                "Charger failure."
946        --#SEVERITY CRITICAL
947        --#SUMMARY "Charger failure has occured."
948::= 37
949
950trapChargerOk TRAP-TYPE
951        ENTERPRISE traps
952        DESCRIPTION
953                "Charger ok."
954        --#SEVERITY INFORMATIONAL
955        --#SUMMARY "Charger is functioning normally."
956::= 38
957
958trapEepromFailure TRAP-TYPE
959        ENTERPRISE traps
960        DESCRIPTION
961                "EEPROM failure."
962        --#SEVERITY CRITICAL
963        --#SUMMARY "EEPROM failure has occured."
964::= 39
965
966trapEepromOk TRAP-TYPE
967        ENTERPRISE traps
968        DESCRIPTION
969                "EEPROM off."
970        --#SEVERITY INFORMATIONAL
971        --#SUMMARY "EEPROM is turned off."
972::= 40
973
974trapShutdownImminent TRAP-TYPE
975        ENTERPRISE traps
976        DESCRIPTION
977                "Shutdown imminent."
978        --#SEVERITY CRITICAL
979        --#SUMMARY "The UPS Shutdown is imminent."
980::= 41
981
982trapShutdownImminentOver TRAP-TYPE
983        ENTERPRISE traps
984        DESCRIPTION
985                "Shutdown imminent over."
986        --#SEVERITY INFORMATIONAL
987        --#SUMMARY "The imminient UPS Shutdown is no longer present."
988::= 42
989
990trapBatteryLow TRAP-TYPE
991        ENTERPRISE traps
992        DESCRIPTION
993                "Battery low."
994        --#SEVERITY CRITICAL
995        --#SUMMARY "UPS battery remaining capacity has fallen below the 'Low Remaining Capacity Threshold' value."
996::= 43
997
998trapBatteryOk TRAP-TYPE
999        ENTERPRISE traps
1000        DESCRIPTION
1001                "Battery ok."
1002        --#SEVERITY INFORMATIONAL
1003        --#SUMMARY "UPS battery remaining capacity is no longer below the 'Under Remaining Capacity Threshold' value."
1004::= 44
1005
1006trapOutputShortCircuit TRAP-TYPE
1007        ENTERPRISE traps
1008        DESCRIPTION
1009                "Output short circuit."
1010        --#SEVERITY CRITICAL
1011        --#SUMMARY "Output short circuit."
1012::= 45
1013
1014trapOutputReturnFromShortCircuit TRAP-TYPE
1015        ENTERPRISE traps
1016        DESCRIPTION
1017                "Output return from short circuit."
1018        --#SEVERITY INFORMATIONAL
1019        --#SUMMARY "Output return from short circuit."
1020::= 46
1021
1022trapUtilityNotPresent TRAP-TYPE
1023        ENTERPRISE traps
1024        DESCRIPTION
1025                "Utility not present."
1026        --#SEVERITY WARNING
1027        --#SUMMARY "Utility is not present."
1028::= 47
1029
1030trapUtilityPresent TRAP-TYPE
1031        ENTERPRISE traps
1032        DESCRIPTION
1033                "Utility present."
1034        --#SEVERITY INFORMATIONAL
1035        --#SUMMARY "Utility is present."
1036::= 48
1037
1038trapBatteryOverVoltage TRAP-TYPE
1039        ENTERPRISE traps
1040        DESCRIPTION
1041                "Battery DC over voltage."
1042        --#SEVERITY CRITICAL
1043        --#SUMMARY "Battery DC Voltage has exceeded the 'Over Voltage Threshold' value."
1044::= 49
1045
1046trapBatteryOverVoltageOk TRAP-TYPE
1047        ENTERPRISE traps
1048        DESCRIPTION
1049                "Battery DC over voltage ok."
1050        --#SEVERITY INFORMATIONAL
1051        --#SUMMARY "Battery DC Voltage is no longer above the 'Over Voltage Threshold' value."
1052::= 50
1053
1054trapHeatsinkOvertemperature TRAP-TYPE
1055        ENTERPRISE traps
1056        DESCRIPTION
1057                "Heatsink overtemperature."
1058        --#SEVERITY CRITICAL
1059        --#SUMMARY "UPS temperature has exceeded the 'Over Temperature Threshold' value."
1060::= 51
1061
1062trapHeatsinkOvertemperatureOk TRAP-TYPE
1063        ENTERPRISE traps
1064        DESCRIPTION
1065                "Heatsink overtemperature ok."
1066        --#SEVERITY INFORMATIONAL
1067        --#SUMMARY "UPS temperature is no longer above the 'Over Temperature Threshold' value."
1068::= 52
1069
1070trapBypassNotAvailable TRAP-TYPE
1071        ENTERPRISE traps
1072        DESCRIPTION
1073                "Bypass not available."
1074        --#SEVERITY WARNING
1075        --#SUMMARY "Bypass is not available."
1076::= 53
1077
1078trapBypassNotAvailableOk TRAP-TYPE
1079        ENTERPRISE traps
1080        DESCRIPTION
1081                "Bypass not available ok."
1082        --#SEVERITY INFORMATIONAL
1083        --#SUMMARY "Bypass is now available."
1084::= 54
1085
1086trapOnManualBypass TRAP-TYPE
1087        ENTERPRISE traps
1088        DESCRIPTION
1089                "On manual/ maintenance bypass."
1090        --#SEVERITY INFORMATIONAL
1091        --#SUMMARY "On manual/ maintenance bypass."
1092::= 55
1093
1094trapUPSOnBattery TRAP-TYPE
1095        ENTERPRISE traps
1096        DESCRIPTION
1097                "UPS on battery."
1098        --#SEVERITY INFORMATIONAL
1099        --#SUMMARY  "UPS on battery."
1100::= 57
1101
1102trapUPSReturnFromBattery TRAP-TYPE
1103        ENTERPRISE traps
1104        DESCRIPTION
1105                "UPS return from battery."
1106        --#SEVERITY INFORMATIONAL
1107        --#SUMMARY "UPS return from battery."
1108::= 58
1109
1110trapUPSOnBypass TRAP-TYPE
1111        ENTERPRISE traps
1112        DESCRIPTION
1113                "UPS on bypass."
1114        --#SEVERITY INFORMATIONAL
1115        --#SUMMARY "UPS on bypass."
1116::= 59
1117
1118trapUPSReturnFromBypass TRAP-TYPE
1119        ENTERPRISE traps
1120        DESCRIPTION
1121                "UPS return from bypass."
1122        --#SEVERITY INFORMATIONAL
1123        --#SUMMARY "UPS return from bypass."
1124::= 60
1125
1126trapBatteryTestInProgress TRAP-TYPE
1127        ENTERPRISE traps
1128        DESCRIPTION
1129                "Battery manual or automatic test in progress."
1130        --#SEVERITY INFORMATIONAL
1131        --#SUMMARY "Battery manual or automatic test in progress."
1132::= 61
1133
1134trapBatteryTestDone TRAP-TYPE
1135        ENTERPRISE traps
1136        VARIABLES { physicalBatteryTestStatus }
1137        DESCRIPTION
1138                "Battery test done."
1139        --#SEVERITY INFORMATIONAL
1140        --#SUMMARY "Battery test done, battery status is: %d."
1141        --#ARGUMENTS {0}
1142::= 62
1143
1144trapBatteryNeedReplacement TRAP-TYPE
1145        ENTERPRISE traps
1146        DESCRIPTION
1147                "Battery test failed, battery needs to be replaced."
1148        --#SEVERITY CRITICAL
1149        --#SUMMARY "Battery test failed, battery needs to be replaced."
1150::= 63
1151
1152trapBatteryReplacementDone TRAP-TYPE
1153        ENTERPRISE traps
1154        DESCRIPTION
1155                "Battery replacement done."
1156        --#SEVERITY INFORMATIONAL
1157        --#SUMMARY "Battery replacement is done."
1158::= 64
1159
1160trapFanFailure TRAP-TYPE
1161        ENTERPRISE traps
1162        DESCRIPTION
1163                "Fan failure."
1164        --#SEVERITY CRITICAL
1165        --#SUMMARY "UPS Fan has failed."
1166::= 65
1167
1168trapFanOk TRAP-TYPE
1169        ENTERPRISE traps
1170        DESCRIPTION
1171                "Fan ok."
1172        --#SEVERITY INFORMATIONAL
1173        --#SUMMARY "UPS Fan is working normally."
1174::= 66
1175
1176trapSiteWiringFault TRAP-TYPE
1177        ENTERPRISE traps
1178        DESCRIPTION
1179                "Site wiring fault."
1180        --#SEVERITY CRITICAL
1181        --#SUMMARY "There is a fault in Site Wiring."
1182::= 67
1183
1184trapSiteWiringOk TRAP-TYPE
1185        ENTERPRISE traps
1186        DESCRIPTION
1187                "Site wiring ok."
1188        --#SEVERITY INFORMATIONAL
1189        --#SUMMARY "No fault found in Site Wiring."
1190::= 68
1191
1192trapBatteryDisconnected TRAP-TYPE
1193        ENTERPRISE traps
1194        DESCRIPTION
1195                "Batteries disconnected."
1196        --#SEVERITY CRITICAL
1197        --#SUMMARY "Batteries have been disconnected from the UPS."
1198::= 69
1199
1200trapBatteryConnected TRAP-TYPE
1201        ENTERPRISE traps
1202        DESCRIPTION
1203                "Batteries connected."
1204        --#SEVERITY INFORMATIONAL
1205        --#SUMMARY "Batteries have been connected to UPS."
1206::= 70
1207
1208trapUPSOff TRAP-TYPE
1209        ENTERPRISE traps
1210        DESCRIPTION
1211                "UPS off."
1212        --#SEVERITY WARNING
1213        --#SUMMARY "UPS has been turned Off."
1214::= 71
1215
1216trapUPSOn TRAP-TYPE
1217        ENTERPRISE traps
1218        DESCRIPTION
1219                "UPS on."
1220        --#SEVERITY WARNING
1221        --#SUMMARY "UPS has been turned On."
1222::= 72
1223
1224trapDCLinkImbalance TRAP-TYPE
1225        ENTERPRISE traps
1226        DESCRIPTION
1227                "DC link imbalance."
1228        --#SEVERITY INFORMATIONAL
1229        --#SUMMARY "UPS has a DC link imbalance."
1230::= 73
1231
1232trapDCLinkImbalanceOk TRAP-TYPE
1233        ENTERPRISE traps
1234        DESCRIPTION
1235                "DC link imbalance ok."
1236        --#SEVERITY INFORMATIONAL
1237        --#SUMMARY "UPS no longer has a DC link imbalance."
1238::= 74
1239
1240trapABMOn TRAP-TYPE
1241        ENTERPRISE traps
1242        VARIABLES { physicalBatteryABMStatus }
1243        DESCRIPTION
1244                "ABM state on."
1245        --#SEVERITY WARNING
1246        --#SUMMARY "ABM is POWERED ON, battery state is : %d"
1247        --#ARGUMENTS {0}
1248::= 79
1249
1250trapABMOff TRAP-TYPE
1251        ENTERPRISE traps
1252        DESCRIPTION
1253                "ABM state off."
1254        --#SEVERITY WARNING
1255        --#SUMMARY "ABM state is POWERED OFF."
1256::= 80
1257
1258trapLoadSegment1Off TRAP-TYPE
1259        ENTERPRISE traps
1260        DESCRIPTION
1261                "Load segment 1 off."
1262        --#SEVERITY WARNING
1263        --#SUMMARY "Load segment 1 is Switched Off."
1264::= 81
1265
1266trapLoadSegment1On TRAP-TYPE
1267        ENTERPRISE traps
1268        DESCRIPTION
1269                "Load segment 1 on."
1270        --#SEVERITY WARNING
1271        --#SUMMARY "Load segment 1 is Switched On."
1272::= 82
1273
1274trapLoadSegment2Off TRAP-TYPE
1275        ENTERPRISE traps
1276        DESCRIPTION
1277                "Load segment 2 off."
1278        --#SEVERITY WARNING
1279        --#SUMMARY "Load segment 2 is Switched Off."
1280::= 83
1281
1282trapLoadSegment2On TRAP-TYPE
1283        ENTERPRISE traps
1284        DESCRIPTION
1285                "Load segment 2 on."
1286        --#SEVERITY WARNING
1287        --#SUMMARY "Load segment 2 is Switched On."
1288::= 84
1289
1290trapInHighEfficiencyMode TRAP-TYPE
1291        ENTERPRISE traps
1292        DESCRIPTION
1293                "In High Efficiency mode."
1294        --#SEVERITY WARNING
1295        --#SUMMARY "UPS is running in High Efficiency mode."
1296::= 85
1297
1298trapReturnFromHighEfficiencyMode TRAP-TYPE
1299        ENTERPRISE traps
1300        DESCRIPTION
1301                "Return from High Efficiency mode."
1302        --#SEVERITY INFORMATIONAL
1303        --#SUMMARY "UPS is no longer running in High Efficiency mode."
1304::= 86
1305
1306trapRectifierOverload TRAP-TYPE
1307        ENTERPRISE traps
1308        DESCRIPTION
1309                "Rectifier input over current."
1310        --#SEVERITY WARNING
1311        --#SUMMARY "Rectifier Input Current has exceeded the 'Input Current Threshold' value."
1312::= 87
1313
1314trapRectifierOverloadOk TRAP-TYPE
1315        ENTERPRISE traps
1316        DESCRIPTION
1317                "Rectifier current ok."
1318        --#SEVERITY INFORMATIONAL
1319        --#SUMMARY "Rectifier current is no longer over 'Input Current Threshold' value."
1320::= 88
1321
1322trapInverterOverload TRAP-TYPE
1323        ENTERPRISE traps
1324        DESCRIPTION
1325                "Inverter output over current."
1326        --#SEVERITY WARNING
1327        --#SUMMARY "Inverter Output Current has exceeded the 'Over Load Threshold' value."
1328::= 89
1329
1330trapInverterOverloadOk TRAP-TYPE
1331        ENTERPRISE traps
1332        DESCRIPTION
1333                "Inverter output current ok."
1334        --#SEVERITY INFORMATIONAL
1335        --#SUMMARY "Inverter Output Current is no longer over 'Ouput Current Threshold' value."
1336::= 90
1337
1338trapBypassVoltageOutOfRange TRAP-TYPE
1339        ENTERPRISE traps
1340        DESCRIPTION
1341                "Bypass AC under or over voltage."
1342        --#SEVERITY WARNING
1343        --#SUMMARY "Bypass AC Voltage has gone out of Normal Range."
1344::= 91
1345
1346trapBypassVoltageOutOfRangeOk TRAP-TYPE
1347        ENTERPRISE traps
1348        DESCRIPTION
1349                "Bypass AC under or over voltage ok."
1350        --#SEVERITY INFORMATIONAL
1351        --#SUMMARY "Bypass AC Voltage has returned back to Normal Range."
1352::= 92
1353
1354trapServiceBattery TRAP-TYPE
1355        ENTERPRISE traps
1356        DESCRIPTION
1357                "Service battery."
1358        --#SEVERITY WARNING
1359        --#SUMMARY "UPS battery needs to be serviced."
1360::= 93
1361
1362trapToBypassCommand TRAP-TYPE
1363        ENTERPRISE traps
1364        DESCRIPTION
1365                "UPS received command to switch on bypass."
1366        --#SEVERITY INFORMATIONAL
1367        --#SUMMARY "UPS received command to switch on bypass."
1368::= 94
1369
1370trapFromBypassCommand TRAP-TYPE
1371        ENTERPRISE traps
1372        DESCRIPTION
1373                "UPS received command to switch on inverter."
1374        --#SEVERITY INFORMATIONAL
1375        --#SUMMARY "UPS received command to switch from bypass to inverter."
1376::= 95
1377
1378trapCommunicationLost TRAP-TYPE
1379        ENTERPRISE traps
1380        DESCRIPTION
1381                "Lost communication with UPS, HID databasis is not updated."
1382        --#SEVERITY WARNING
1383        --#SUMMARY "UMC lost communication with UPS, HID databasis is not updated."
1384::= 96
1385
1386trapCommunicationRestored TRAP-TYPE
1387        ENTERPRISE traps
1388        DESCRIPTION
1389                "Communication restored with UPS, HID databasis is updated."
1390        --#SEVERITY INFORMATIONAL
1391        --#SUMMARY "Communication restored with UPS."
1392::= 97
1393
1394-- 01.04.0001 Release on 2011/07/28 : Traps 98 to 111 added for the environment sensor.
1395
1396trapEnvironComFailure TRAP-TYPE
1397        ENTERPRISE traps
1398        DESCRIPTION
1399                "Environment Probe communication failure."
1400       --#SEVERITY WARNING
1401       --#SUMMARY "Environment Probe communication failure."
1402::= 98
1403
1404trapEnvironComOK TRAP-TYPE
1405        ENTERPRISE traps
1406        DESCRIPTION
1407                "Environment Probe communication restored."
1408       --#SEVERITY INFORMATIONAL
1409       --#SUMMARY "Environment Probe communication restored."
1410::= 99
1411
1412trapEnvironTemperatureLow TRAP-TYPE
1413        ENTERPRISE traps
1414        DESCRIPTION
1415                "Temperature is below low threshold."
1416       --#SEVERITY WARNING
1417       --#SUMMARY "Temperature is below low threshold."
1418::= 100
1419
1420trapEnvironTemperatureHigh TRAP-TYPE
1421        ENTERPRISE traps
1422        DESCRIPTION
1423                "Temperature is above high threshold."
1424       --#SEVERITY WARNING
1425       --#SUMMARY "Temperature is above high threshold."
1426::= 102
1427
1428trapEnvironTemperatureOK TRAP-TYPE
1429        ENTERPRISE traps
1430        DESCRIPTION
1431                "Temperature is in normal range."
1432       --#SEVERITY INFORMATIONAL
1433       --#SUMMARY "Temperature is in normal range."
1434::= 103
1435
1436trapEnvironHumidityLow TRAP-TYPE
1437       ENTERPRISE traps
1438       DESCRIPTION
1439                "Humidity is below low threshold."
1440       --#SEVERITY WARNING
1441       --#SUMMARY "Humidity is below low threshold."
1442::= 104
1443
1444trapEnvironHumidityHigh TRAP-TYPE
1445        ENTERPRISE traps
1446        DESCRIPTION
1447                "Humidity is above high threshold."
1448       --#SEVERITY WARNING
1449       --#SUMMARY "Humidity is above high threshold."
1450::= 106
1451
1452trapEnvironHumidityOK TRAP-TYPE
1453        ENTERPRISE traps
1454        DESCRIPTION
1455                "Humidity is in normal range."
1456       --#SEVERITY INFORMATIONAL
1457       --#SUMMARY "Humidity is in normal range."
1458::= 107
1459
1460trapEnvironInput1Closed TRAP-TYPE
1461        ENTERPRISE traps
1462        DESCRIPTION
1463                "Input #1 is Closed."
1464       --#SEVERITY INFORMATIONAL
1465       --#SUMMARY "Input #1 is Closed."
1466::= 108
1467
1468trapEnvironInput1Open TRAP-TYPE
1469        ENTERPRISE traps
1470        DESCRIPTION
1471                "Input #1 is Open."
1472       --#SEVERITY INFORMATIONAL
1473       --#SUMMARY "Input #1 is Open."
1474::= 109
1475
1476trapEnvironInput2Closed TRAP-TYPE
1477        ENTERPRISE traps
1478        DESCRIPTION
1479                "Input #2 is Closed."
1480       --#SEVERITY INFORMATIONAL
1481       --#SUMMARY "Input #2 is Closed."
1482::= 110
1483
1484trapEnvironInput2Open TRAP-TYPE
1485        ENTERPRISE traps
1486        DESCRIPTION
1487                "Input #2 is Open."
1488       --#SEVERITY INFORMATIONAL
1489       --#SUMMARY "Input #2 is Open."
1490::= 111
1491END
1492