1 2-- Eltek OEM MIB for Nextel Digital Power plant designs 3 4ELTEK_GENERIC-MIB DEFINITIONS ::= BEGIN 5 6IMPORTS 7 NOTIFICATION-TYPE, OBJECT-TYPE, MODULE-IDENTITY, 8 mib-2, enterprises, Integer32 9 FROM SNMPv2-SMI 10 NOTIFICATION-GROUP 11 FROM SNMPv2-CONF 12 DisplayString 13 FROM SNMPv2-TC 14 eltek 15 FROM ELTEK_COMMON-MIB; 16 17 18-- Aeongold branch will be 1 19-- AL175 branch will be 2 20-- AL6000 branch will be 3 21-- Webpower proto branch will be 4 22-- ENEXUS branch will be 5 23-- Nextel Smartpack branch will be 6 24-- ELTEK Common branch will be 7 25 26eltekPlant OBJECT IDENTIFIER ::= { eltek 7 } 27 28-- This branch contains OIDs for configuration of the Smartpack Control System's 29-- basic data and settings 30 31controlSystem OBJECT IDENTIFIER ::= { eltekPlant 1 } 32systemTime OBJECT IDENTIFIER ::= { controlSystem 1 } 33 34-- This branch contains OIDs for configuration of the DC Power System's 35-- basic factory data and user's installation settings 36 37dcSystem OBJECT IDENTIFIER ::= { eltekPlant 2 } 38dcPlant OBJECT IDENTIFIER ::= { dcSystem 1 } 39 40-- This branch contains OIDs for configuration of the DC Power System's 41-- installation and location settings 42 43systemSiteInfo OBJECT IDENTIFIER ::= { dcPlant 3 } 44 45-- This branch contains OIDs for configuration of the DC Power System's 46-- Battery charging and protection related settings 47 48battery OBJECT IDENTIFIER ::= { eltekPlant 3 } 49 50-- This branch contains OIDs for configuration of the DC Power System's 51-- Battery Disconnect Contactor / Emergency Disconnect related settings 52 53batteryLVD OBJECT IDENTIFIER ::= { battery 17 } 54 55-- This branch contains OIDs for configuration of the DC Power System's 56-- Battery Symmetry Monitor related settings 57 58batteryMidpoint OBJECT IDENTIFIER ::= { battery 18 } 59 60-- This branch contains OIDs related to the DC Load Distribution equipment 61 62loadDistribution OBJECT IDENTIFIER ::= { eltekPlant 4 } 63 64-- This branch contains OIDs related to the Load Disconnect / Load Shedding equipment 65 66loadDistributionLVDStatus OBJECT IDENTIFIER ::= { loadDistribution 3 } 67 68-- This branch contains OIDs related to the Flatpack 2 rectifier parameters 69 70rectifier OBJECT IDENTIFIER ::= { eltekPlant 5 } 71 72-- This branch contains OIDs for polling of the Flatpack 2 Rectifier status settings 73 74rectifierStatus OBJECT IDENTIFIER ::= { rectifier 5 } 75acDistribution OBJECT IDENTIFIER ::= { eltekPlant 6 } 76 77-- This branch contains Alarms and Events that are mappable to alarm relay positions. 78-- Also duplicated as Traps 79 80alarmGroup OBJECT IDENTIFIER ::= { eltekPlant 7 } 81 82-- Common alarm types: (12) as specified by Nextel as relay outputs, 83-- others available for inclusion to Plant summation alarms 84 85alarmWellknownAlarms OBJECT IDENTIFIER ::= { alarmGroup 1 } 86 87systemTimeTime OBJECT-TYPE 88 SYNTAX DisplayString (SIZE(0..255)) 89 MAX-ACCESS read-only 90 STATUS current 91 DESCRIPTION 92 "The system date and time. Used for event timestamps and logging" 93 ::= { systemTime 1 } 94 95systemInfoRefresh OBJECT-TYPE 96 SYNTAX INTEGER { 97 pushbutton (0), 98 refreshdata (1) 99 } 100 MAX-ACCESS read-write 101 STATUS current 102 DESCRIPTION 103 "This object will re-initialize the agent, updating MIB data values." 104 ::= { controlSystem 2 } 105 106systemTrapRepeatRate OBJECT-TYPE 107 SYNTAX Integer32 (0..10) 108 MAX-ACCESS read-write 109 STATUS current 110 DESCRIPTION 111 "This object sets the repeat rate of any active traps, in seconds. 112 Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event." 113 ::= { controlSystem 3 } 114 115systemSendOffTrap OBJECT-TYPE 116 SYNTAX INTEGER { 117 off (0), 118 on (1) 119 } 120 MAX-ACCESS read-write 121 STATUS current 122 DESCRIPTION 123 "A separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. 124 Entering 0 (zero) will prevent OFF traps from being transmitted." 125 ::= { controlSystem 4 } 126 127systemSiteInfoCustomer OBJECT-TYPE 128 SYNTAX DisplayString (SIZE(0..32)) 129 MAX-ACCESS read-only 130 STATUS current 131 DESCRIPTION 132 "The Customer name (as stored in the Smartpack Control Unit)" 133 ::= { systemSiteInfo 1 } 134 135systemSiteInfoLocation OBJECT-TYPE 136 SYNTAX DisplayString (SIZE(0..32)) 137 MAX-ACCESS read-only 138 STATUS current 139 DESCRIPTION 140 "The system/site Location details (as stored in the Smartpack Control Unit)." 141 ::= { systemSiteInfo 2 } 142 143systemSiteInfoMessage1 OBJECT-TYPE 144 SYNTAX DisplayString (SIZE(0..32)) 145 MAX-ACCESS read-only 146 STATUS current 147 DESCRIPTION 148 "The system/site Info Message record #1 (as stored in the Smartpack Control Unit). 31 Bytes." 149 ::= { systemSiteInfo 3 } 150 151systemSiteInfoMessage2 OBJECT-TYPE 152 SYNTAX DisplayString (SIZE(0..32)) 153 MAX-ACCESS read-only 154 STATUS current 155 DESCRIPTION 156 "The system/site Info Message record #2 (as stored in the Smartpack Control Unit). 31 Bytes." 157 ::= { systemSiteInfo 4 } 158 159systemSiteInfoInstalledDate OBJECT-TYPE 160 SYNTAX DisplayString (SIZE(0..16)) 161 MAX-ACCESS read-only 162 STATUS current 163 DESCRIPTION 164 "The system's Installed Date text string (as stored in the Smartpack Control Unit) 16bytes." 165 ::= { systemSiteInfo 5 } 166 167systemSiteInfoControllerType OBJECT-TYPE 168 SYNTAX INTEGER { 169 al175 (0), 170 al4000 (1), 171 al6000 (2), 172 enexus (3) 173 } 174 MAX-ACCESS read-only 175 STATUS current 176 DESCRIPTION 177 "The system Controller Module currently connected. 178 AL175/MCU=0; AEON Gold=1; AL6000=2; Smartpack=3" 179 ::= { systemSiteInfo 6 } 180 181systemSiteInfoSystemSeriaNum OBJECT-TYPE 182 SYNTAX DisplayString (SIZE(0..16)) 183 MAX-ACCESS read-only 184 STATUS current 185 DESCRIPTION 186 "The serial number for the complete system" 187 ::= { systemSiteInfo 7 } 188 189systemSiteInfoControllerSeriaNum OBJECT-TYPE 190 SYNTAX DisplayString (SIZE(0..16)) 191 MAX-ACCESS read-only 192 STATUS current 193 DESCRIPTION 194 "The serial number for the system controller" 195 ::= { systemSiteInfo 8 } 196 197systemNominalVoltage OBJECT-TYPE 198 SYNTAX INTEGER { 199 prs48v (0), 200 prs24v (1), 201 prs12v (2), 202 prs26v (3), 203 prs60v (4) 204 } 205 MAX-ACCESS read-only 206 STATUS current 207 DESCRIPTION 208 "The nominal voltage rating. 12V/24V/48V/60V systems 209 0=48V 210 1=24V 211 2=12V 212 3=26V 213 4=60V" 214 ::= { dcPlant 4 } 215 216systemOperationalStatus OBJECT-TYPE 217 SYNTAX INTEGER { 218 floatvoltreg (0), 219 floattempcomp (1), 220 batteryboost (2), 221 batterytest (3) 222 } 223 MAX-ACCESS read-only 224 STATUS current 225 DESCRIPTION 226 "A summary status showing if the system is testing, boosting, floating etc. 227 0=Float, voltage regulated 228 1=Float, temperature comp. regulated; 229 2=equalize 230 3=battery test" 231 ::= { dcSystem 2 } 232 233batteryName OBJECT-TYPE 234 SYNTAX DisplayString (SIZE(0..16)) 235 MAX-ACCESS read-only 236 STATUS current 237 DESCRIPTION 238 "A descriptive name of the battery installed in the system" 239 ::= { battery 1 } 240 241batteryVoltage OBJECT-TYPE 242 SYNTAX Integer32 (0..7500) 243 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 244 MAX-ACCESS read-only 245 STATUS current 246 DESCRIPTION 247 "The measured battery voltage." 248 ::= { battery 2 } 249 250batteryCurrent OBJECT-TYPE 251 SYNTAX Integer32 252 UNITS "Amperes; i.e. 20 = 20 Amperes" 253 MAX-ACCESS read-only 254 STATUS current 255 DESCRIPTION 256 "The measured battery current." 257 ::= { battery 3 } 258 259batteryTemp OBJECT-TYPE 260 SYNTAX Integer32 (0..9999) 261 UNITS "1/10 Deg. C; i.e. 250 = 25.0 Deg. C." 262 MAX-ACCESS read-only 263 STATUS current 264 DESCRIPTION 265 "The battery temperature " 266 ::= { battery 4 } 267 268batteryBreakerStatus OBJECT-TYPE 269 SYNTAX INTEGER { 270 closed (0), 271 open (1) 272 } 273 MAX-ACCESS read-only 274 STATUS current 275 DESCRIPTION 276 "The state of the battery fuse/breaker can be either closed(0) or open(1) " 277 ::= { battery 5 } 278 279batteryChargeCurrentLimitCtrl OBJECT-TYPE 280 SYNTAX INTEGER { 281 deactivate (0), 282 activate (1) 283 } 284 MAX-ACCESS read-write 285 STATUS current 286 DESCRIPTION 287 "Control field for the battery charge limitation feature; 0=inactive, 1=active." 288 ::= { battery 6 } 289 290batteryChargeCurrentLimitValue OBJECT-TYPE 291 SYNTAX Integer32 (0..2100) 292 UNITS "Amperes; i.e. 20 = 20 Amperes" 293 MAX-ACCESS read-write 294 STATUS current 295 DESCRIPTION 296 "Battery charging current limit value" 297 ::= { battery 7 } 298 299batteryTempCompEnable OBJECT-TYPE 300 SYNTAX INTEGER { 301 disable (0), 302 enable (1) 303 } 304 MAX-ACCESS read-write 305 STATUS current 306 DESCRIPTION 307 "Enable (0) or Disable (1) Battery Temperature Compensated output regulation mode" 308 ::= { battery 8 } 309 310batteryFloatVoltConfig OBJECT-TYPE 311 SYNTAX Integer32 (4300..6000) 312 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 313 MAX-ACCESS read-write 314 STATUS current 315 DESCRIPTION 316 "The Voltage at which the DC System float charges." 317 ::= { battery 9 } 318 319batteryEqualizeVoltConfig OBJECT-TYPE 320 SYNTAX Integer32 (4300..6000) 321 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 322 MAX-ACCESS read-write 323 STATUS current 324 DESCRIPTION 325 "The Voltage at which the DC System boost charges the batteries." 326 ::= { battery 10 } 327 328batteryHighMajorAlarmVoltageConfig OBJECT-TYPE 329 SYNTAX Integer32 330 MAX-ACCESS read-write 331 STATUS current 332 DESCRIPTION 333 "The High Battery Voltage alarm limit set voltage" 334 ::= { battery 11 } 335 336batteryHighMinorAlarmVoltageConfig OBJECT-TYPE 337 SYNTAX Integer32 338 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 339 MAX-ACCESS read-write 340 STATUS current 341 DESCRIPTION 342 "The High Battery Voltage alarm limit set voltage" 343 ::= { battery 12 } 344 345batteryLowMajorAlarmVoltageConfig OBJECT-TYPE 346 SYNTAX Integer32 347 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 348 MAX-ACCESS read-write 349 STATUS current 350 DESCRIPTION 351 "The Low Battery Voltage Alarm limit set voltage" 352 ::= { battery 13 } 353 354-- This alarm may be used to warn of impending Low Voltage Battery Disconnect operation 355 356batteryLowMinorAlarmVoltageConfig OBJECT-TYPE 357 SYNTAX Integer32 358 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 359 MAX-ACCESS read-write 360 STATUS current 361 DESCRIPTION 362 "The Very Low Battery Voltage Alarm limit set voltage" 363 ::= { battery 14 } 364 365batteryStartManualTest OBJECT-TYPE 366 SYNTAX INTEGER { 367 pushbutton (0), 368 starttest (1), 369 stoptest (2) 370 } 371 MAX-ACCESS read-write 372 STATUS current 373 DESCRIPTION 374 "This pushbutton will start a manual battery test if otherwise the system allows it." 375 ::= { battery 15 } 376 377batteryStartManualBoost OBJECT-TYPE 378 SYNTAX INTEGER { 379 pushbutton (0), 380 startboost (1), 381 stopboost (2) 382 } 383 MAX-ACCESS read-write 384 STATUS current 385 DESCRIPTION 386 "This pushbutton will start a manual battery boost if otherwise the system allows it." 387 ::= { battery 16 } 388 389batteryLVDStatus OBJECT-TYPE 390 SYNTAX INTEGER { 391 connect (0), 392 disconnect (1), 393 disable (2) 394 } 395 MAX-ACCESS read-only 396 STATUS current 397 DESCRIPTION 398 "Contactor is closed(0) or open(1) " 399 ::= { batteryLVD 1 } 400 401batteryLVDDisconnectVoltage OBJECT-TYPE 402 SYNTAX Integer32 (0..7200) 403 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 404 MAX-ACCESS read-write 405 STATUS current 406 DESCRIPTION 407 "The Contactor Disconnect Voltage" 408 ::= { batteryLVD 2 } 409 410batteryLVDConnectVoltage OBJECT-TYPE 411 SYNTAX Integer32 (0..7200) 412 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 413 MAX-ACCESS read-write 414 STATUS current 415 DESCRIPTION 416 "The Contactor Reconnect Voltage" 417 ::= { batteryLVD 3 } 418 419-- This setpoint / value is common for all battery strings monitored 420 421batteryMidpointDeltaLimitVoltage OBJECT-TYPE 422 SYNTAX Integer32 423 UNITS "1/100 Volt; i.e. 25 = 2.50V" 424 MAX-ACCESS read-write 425 STATUS current 426 DESCRIPTION 427 "The allowable deviation of the midpoint battery voltage from the theoretical. 428 Exceeding this value in either direction (+/-) causes an alarm state" 429 ::= { batteryMidpoint 1 } 430 431batteryMidpointIndex OBJECT-TYPE 432 SYNTAX Integer32 (1..8) 433 MAX-ACCESS read-only 434 STATUS current 435 DESCRIPTION 436 "An index of Battery Strings, for the batteryMidpointControlTable 437 and batteryMidpointStatusTable arrays " 438 ::= { batteryMidpoint 2 } 439 440batteryMidpointControlTable OBJECT-TYPE 441 SYNTAX SEQUENCE OF BatteryMidpointControlEntry 442 MAX-ACCESS not-accessible 443 STATUS current 444 DESCRIPTION 445 "A table of settings related to Battery Symmetry (midpoint) Monitoring" 446 ::= { batteryMidpoint 3 } 447 448batteryMidpointControlEntry OBJECT-TYPE 449 SYNTAX BatteryMidpointControlEntry 450 MAX-ACCESS not-accessible 451 STATUS current 452 DESCRIPTION 453 "Settings related to Battery Symmetry (midpoint) Monitoring, corresponding 454 to the batteryMidpointIndex value" 455 INDEX { batteryMidpointIndex } 456 ::= { batteryMidpointControlTable 1 } 457 458BatteryMidpointControlEntry ::= SEQUENCE { 459 midpointEnableID 460 Integer32, 461 midpointEnable 462 INTEGER 463} 464 465midpointEnableID OBJECT-TYPE 466 SYNTAX Integer32 (1..8) 467 MAX-ACCESS read-only 468 STATUS current 469 DESCRIPTION 470 "The rectifier ID number of the rectifier record." 471 ::= { batteryMidpointControlEntry 1 } 472 473midpointEnable OBJECT-TYPE 474 SYNTAX INTEGER { 475 disable (0), 476 enable (1) 477 } 478 MAX-ACCESS read-write 479 STATUS current 480 DESCRIPTION 481 "Enable (1) or Disable (0) the Battery Monitor channel which corresponds 482 to the batteryMidpointIndex value" 483 ::= { batteryMidpointControlEntry 2 } 484 485batteryMidpointStatusTable OBJECT-TYPE 486 SYNTAX SEQUENCE OF BatteryMidpointStatusEntry 487 MAX-ACCESS not-accessible 488 STATUS current 489 DESCRIPTION 490 "A table of values and/or measurements related to Battery Symmetry (midpoint) Monitoring" 491 ::= { batteryMidpoint 4 } 492 493batteryMidpointStatusEntry OBJECT-TYPE 494 SYNTAX BatteryMidpointStatusEntry 495 MAX-ACCESS not-accessible 496 STATUS current 497 DESCRIPTION 498 "Values related to Battery Symmetry (midpoint) Monitoring, corresponding 499 to the batteryMidpointIndex value" 500 INDEX { batteryMidpointIndex } 501 ::= { batteryMidpointStatusTable 1 } 502 503BatteryMidpointStatusEntry ::= SEQUENCE { 504 midpointStatusID 505 Integer32, 506 midpointStatus 507 INTEGER, 508 midpointDeltaVoltage 509 Integer32 510} 511 512midpointStatusID OBJECT-TYPE 513 SYNTAX Integer32 (1..8) 514 MAX-ACCESS read-only 515 STATUS current 516 DESCRIPTION 517 "The rectifier ID number of the rectifier record." 518 ::= { batteryMidpointStatusEntry 1 } 519 520midpointStatus OBJECT-TYPE 521 SYNTAX INTEGER { 522 ok (0), 523 alarm (1), 524 disable (2) 525 } 526 MAX-ACCESS read-only 527 STATUS current 528 DESCRIPTION 529 "Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds 530 to the batteryMidpointIndex value" 531 ::= { batteryMidpointStatusEntry 2 } 532 533midpointDeltaVoltage OBJECT-TYPE 534 SYNTAX Integer32 535 UNITS "1/100 Volt; i.e. 25 = 2.5V." 536 MAX-ACCESS read-only 537 STATUS current 538 DESCRIPTION 539 "The measured battery voltage deviation from midpoint of the Battery Monitor channel 540 which corresponds to the batteryMidpointIndex value." 541 ::= { batteryMidpointStatusEntry 3 } 542 543loadDistributionCurrent OBJECT-TYPE 544 SYNTAX Integer32 545 UNITS "Amperes; i.e. 20 = 20 Amperes" 546 MAX-ACCESS read-only 547 STATUS current 548 DESCRIPTION 549 "The total load current" 550 ::= { loadDistribution 1 } 551 552loadDistributionBreakerStatus OBJECT-TYPE 553 SYNTAX INTEGER { 554 closed (0), 555 open (1) 556 } 557 MAX-ACCESS read-only 558 STATUS current 559 DESCRIPTION 560 "The state of the load fuse/breaker can be either closed(0) or open(1) " 561 ::= { loadDistribution 2 } 562 563loadLVD1EnableStatus OBJECT-TYPE 564 SYNTAX INTEGER { 565 disabled (0), 566 enabled (1) 567 } 568 MAX-ACCESS read-only 569 STATUS current 570 DESCRIPTION 571 "The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use." 572 ::= { loadDistributionLVDStatus 1 } 573 574loadLVD1Status OBJECT-TYPE 575 SYNTAX INTEGER { 576 connect (0), 577 disconnect (1), 578 disable (2) 579 } 580 MAX-ACCESS read-only 581 STATUS current 582 DESCRIPTION 583 "The A Bus (primary loads) Contactor is closed(0) or open(1) " 584 ::= { loadDistributionLVDStatus 2 } 585 586loadLVD1ConnectVoltage OBJECT-TYPE 587 SYNTAX Integer32 (0..7200) 588 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 589 MAX-ACCESS read-write 590 STATUS current 591 DESCRIPTION 592 "The A Bus (primary loads) Contactor Connect Voltage" 593 ::= { loadDistributionLVDStatus 3 } 594 595loadLVD1DisconnectVoltage OBJECT-TYPE 596 SYNTAX Integer32 (0..7200) 597 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 598 MAX-ACCESS read-write 599 STATUS current 600 DESCRIPTION 601 "The A Bus (primary loads) Contactor Disconnect Voltage" 602 ::= { loadDistributionLVDStatus 4 } 603 604loadLVD2EnableStatus OBJECT-TYPE 605 SYNTAX INTEGER { 606 disabled (0), 607 enabled (1) 608 } 609 MAX-ACCESS read-only 610 STATUS current 611 DESCRIPTION 612 "The status of contactors configuration. 'enabled' means that the contactor is i n use. 613 'disabled' means that the contactor is disconfigured and not in use." 614 ::= { loadDistributionLVDStatus 5 } 615 616loadLVD2Status OBJECT-TYPE 617 SYNTAX INTEGER { 618 connect (0), 619 disconnect (1), 620 disable (2) 621 } 622 MAX-ACCESS read-only 623 STATUS current 624 DESCRIPTION 625 "The B Bus (secondary loads) Contactor is closed(0) or open(1) " 626 ::= { loadDistributionLVDStatus 6 } 627 628loadLVD2ConnectVoltage OBJECT-TYPE 629 SYNTAX Integer32 (0..7200) 630 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 631 MAX-ACCESS read-write 632 STATUS current 633 DESCRIPTION 634 "The B Bus (secondary loads) Contactor Connect Voltage" 635 ::= { loadDistributionLVDStatus 7 } 636 637loadLVD2DisconnectVoltage OBJECT-TYPE 638 SYNTAX Integer32 (0..7200) 639 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 640 MAX-ACCESS read-write 641 STATUS current 642 DESCRIPTION 643 "The B Bus (secondary loads) Contactor Disconnect Voltage" 644 ::= { loadDistributionLVDStatus 8 } 645 646loadLVD3EnableStatus OBJECT-TYPE 647 SYNTAX INTEGER { 648 disabled (0), 649 enabled (1) 650 } 651 MAX-ACCESS read-only 652 STATUS current 653 DESCRIPTION 654 "The status of contactors configuration. 'enabled' means that the contactor is i n use. 655 'disabled' means that the contactor is disconfigured and not in use." 656 ::= { loadDistributionLVDStatus 9 } 657 658loadLVD3Status OBJECT-TYPE 659 SYNTAX INTEGER { 660 connect (0), 661 disconnect (1), 662 disable (2) 663 } 664 MAX-ACCESS read-only 665 STATUS current 666 DESCRIPTION 667 "The C Bus (critical loads) Contactor is closed(0) or open(1) " 668 ::= { loadDistributionLVDStatus 10 } 669 670loadLVD3ConnectVoltage OBJECT-TYPE 671 SYNTAX Integer32 (0..7200) 672 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 673 MAX-ACCESS read-write 674 STATUS current 675 DESCRIPTION 676 "The C Bus (critical loads) Contactor Connect Voltage" 677 ::= { loadDistributionLVDStatus 11 } 678 679loadLVD3DisconnectVoltage OBJECT-TYPE 680 SYNTAX Integer32 (0..7200) 681 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 682 MAX-ACCESS read-write 683 STATUS current 684 DESCRIPTION 685 "The C Bus (critical loads) Contactor Disconnect Voltage" 686 ::= { loadDistributionLVDStatus 12 } 687 688rectifierInstalledRectifiers OBJECT-TYPE 689 SYNTAX Integer32 (1..101) 690 MAX-ACCESS read-only 691 STATUS current 692 DESCRIPTION 693 "The installed number of rectifiers for this DC Power System." 694 ::= { rectifier 1 } 695 696rectifierRectifiersActive OBJECT-TYPE 697 SYNTAX Integer32 (1..101) 698 MAX-ACCESS read-only 699 STATUS current 700 DESCRIPTION 701 "The actual number of active rectifiers in this DC Power System." 702 ::= { rectifier 2 } 703 704rectifierTotalCurrent OBJECT-TYPE 705 SYNTAX Integer32 706 UNITS "Amperes; i.e. 20 = 20 Amperes" 707 MAX-ACCESS read-only 708 STATUS current 709 DESCRIPTION 710 "The DC system's total available current" 711 ::= { rectifier 3 } 712 713rectifierUtilization OBJECT-TYPE 714 SYNTAX Integer32 (0..100) 715 MAX-ACCESS read-only 716 STATUS current 717 DESCRIPTION 718 "Utilization in % of available rectifier capacity" 719 ::= { rectifier 4 } 720 721rectifierStatusNoIndex OBJECT-TYPE 722 SYNTAX Integer32 (1..20) 723 MAX-ACCESS read-write 724 STATUS current 725 DESCRIPTION 726 "A starting index for the rectifierStatusTable array" 727 DEFVAL { 1 } 728 ::= { rectifierStatus 1 } 729 730rectifierStatusTable OBJECT-TYPE 731 SYNTAX SEQUENCE OF RectifierStatusEntry 732 MAX-ACCESS not-accessible 733 STATUS current 734 DESCRIPTION 735 "A table listing up to sixteen sequential recifiers, starting 736 from the rectifier number specified by rectifierStatusNoIndex" 737 ::= { rectifierStatus 2 } 738 739rectifierStatusEntry OBJECT-TYPE 740 SYNTAX RectifierStatusEntry 741 MAX-ACCESS not-accessible 742 STATUS current 743 DESCRIPTION 744 "A row of rectifier status data corresponding to the rectifierStatusNoIndex value" 745 INDEX { rectifierStatusID } 746 ::= { rectifierStatusTable 1 } 747 748RectifierStatusEntry ::= SEQUENCE { 749 rectifierStatusID 750 Integer32, 751 rectifierStatusStatus 752 INTEGER, 753 rectifierStatusOutputCurrent 754 Integer32, 755 rectifierStatusOutputVoltage 756 Integer32, 757 rectifierStatusTemp 758 Integer32, 759 rectifierStatusType 760 DisplayString, 761 rectifierStatusSKU 762 DisplayString, 763 rectifierStatusSerialNo 764 DisplayString, 765 rectifierStatusRevisionLevel 766 DisplayString 767} 768 769rectifierStatusID OBJECT-TYPE 770 SYNTAX Integer32 (1..100) 771 MAX-ACCESS read-only 772 STATUS current 773 DESCRIPTION 774 "The rectifier ID number of the rectifier record." 775 ::= { rectifierStatusEntry 1 } 776 777rectifierStatusStatus OBJECT-TYPE 778 SYNTAX INTEGER { 779 absent (0), 780 active (1), 781 failed (2), 782 walkin (3), 783 disabledbycommand (4) 784 } 785 MAX-ACCESS read-only 786 STATUS current 787 DESCRIPTION 788 "The operational status of the rectifier record. 789 absent (0), 790 active (1), 791 failed (2), 792 walkin (3), 793 disabledbycommand (4) 794 795 " 796 ::= { rectifierStatusEntry 2 } 797 798rectifierStatusOutputCurrent OBJECT-TYPE 799 SYNTAX Integer32 (0..65535) 800 UNITS "1/10 Amperes; i.e. 200 = 20 Amperes" 801 MAX-ACCESS read-only 802 STATUS current 803 DESCRIPTION 804 "The rectifier current of the rectifier record." 805 ::= { rectifierStatusEntry 3 } 806 807rectifierStatusOutputVoltage OBJECT-TYPE 808 SYNTAX Integer32 (0..65535) 809 UNITS "1/100 Volt; i.e. 5400 = 54.00V" 810 MAX-ACCESS read-only 811 STATUS current 812 DESCRIPTION 813 "The rectifier voltage of the rectifier record." 814 ::= { rectifierStatusEntry 4 } 815 816rectifierStatusTemp OBJECT-TYPE 817 SYNTAX Integer32 (0..65535) 818 UNITS "Deg. C/10; i.e. 350 = 35.0 Deg. C" 819 MAX-ACCESS read-only 820 STATUS current 821 DESCRIPTION 822 "The heatsink temperature of the rectifier record." 823 ::= { rectifierStatusEntry 5 } 824 825rectifierStatusType OBJECT-TYPE 826 SYNTAX DisplayString (SIZE(0..16)) 827 MAX-ACCESS read-only 828 STATUS current 829 DESCRIPTION 830 "The rectifier article number string of the rectifier record." 831 ::= { rectifierStatusEntry 6 } 832 833rectifierStatusSKU OBJECT-TYPE 834 SYNTAX DisplayString (SIZE(0..16)) 835 MAX-ACCESS read-only 836 STATUS current 837 DESCRIPTION 838 "The rectifier Stock Keeping Unit number or other user-defined ID of the rectifier record." 839 ::= { rectifierStatusEntry 7 } 840 841rectifierStatusSerialNo OBJECT-TYPE 842 SYNTAX DisplayString (SIZE(0..16)) 843 MAX-ACCESS read-only 844 STATUS current 845 DESCRIPTION 846 "The rectifier serial number string of the rectifier record." 847 ::= { rectifierStatusEntry 8 } 848 849rectifierStatusRevisionLevel OBJECT-TYPE 850 SYNTAX DisplayString (SIZE(0..16)) 851 MAX-ACCESS read-only 852 STATUS current 853 DESCRIPTION 854 "The rectifier version number string of the rectifier record." 855 ::= { rectifierStatusEntry 9 } 856 857acVoltage1 OBJECT-TYPE 858 SYNTAX Integer32 859 UNITS "Volts AC" 860 MAX-ACCESS read-only 861 STATUS current 862 DESCRIPTION 863 "The AC Voltage of phase 1" 864 ::= { acDistribution 1 } 865 866acVoltage2 OBJECT-TYPE 867 SYNTAX Integer32 868 UNITS "Volts AC" 869 MAX-ACCESS read-only 870 STATUS current 871 DESCRIPTION 872 "The AC Voltage of phase 2" 873 ::= { acDistribution 2 } 874 875acVoltage3 OBJECT-TYPE 876 SYNTAX Integer32 877 UNITS "Volts AC" 878 MAX-ACCESS read-only 879 STATUS current 880 DESCRIPTION 881 "The AC Voltage of phase 3" 882 ::= { acDistribution 3 } 883 884alarmMajorHighBattVolt OBJECT-TYPE 885 SYNTAX INTEGER { 886 normal (0), 887 alarm (1) 888 } 889 MAX-ACCESS read-only 890 STATUS current 891 DESCRIPTION 892 "The Very High Battery Voltage Alarm" 893 ::= { alarmWellknownAlarms 1 } 894 895alarmMinorHighBattVolt OBJECT-TYPE 896 SYNTAX INTEGER { 897 normal (0), 898 alarm (1) 899 } 900 MAX-ACCESS read-only 901 STATUS current 902 DESCRIPTION 903 "The High Battery Voltage alarm" 904 ::= { alarmWellknownAlarms 2 } 905 906alarmMajorLowBattVolt OBJECT-TYPE 907 SYNTAX INTEGER { 908 normal (0), 909 alarm (1) 910 } 911 MAX-ACCESS read-only 912 STATUS current 913 DESCRIPTION 914 "The Very Low Battery Voltage Alarm" 915 ::= { alarmWellknownAlarms 3 } 916 917alarmMinorLowBattVolt OBJECT-TYPE 918 SYNTAX INTEGER { 919 normal (0), 920 alarm (1) 921 } 922 MAX-ACCESS read-only 923 STATUS current 924 DESCRIPTION 925 "The Low Battery Voltage Alarm" 926 ::= { alarmWellknownAlarms 4 } 927 928alarmMajorBatteryHighTemp OBJECT-TYPE 929 SYNTAX INTEGER { 930 normal (0), 931 alarm (1) 932 } 933 MAX-ACCESS read-only 934 STATUS current 935 DESCRIPTION 936 "Temperature much too high alarm, or temperature compensation circuit / probe failure alarm" 937 ::= { alarmWellknownAlarms 5 } 938 939alarmMinorBatteryHighTemp OBJECT-TYPE 940 SYNTAX INTEGER { 941 normal (0), 942 alarm (1) 943 } 944 MAX-ACCESS read-only 945 STATUS current 946 DESCRIPTION 947 "Temperature much too high alarm" 948 ::= { alarmWellknownAlarms 6 } 949 950alarmBatteryDisconnectOpen OBJECT-TYPE 951 SYNTAX INTEGER { 952 normal (0), 953 alarm (1) 954 } 955 MAX-ACCESS read-only 956 STATUS current 957 DESCRIPTION 958 "The Battery Disconnect Contactor alarm" 959 ::= { alarmWellknownAlarms 7 } 960 961alarmLVD1open OBJECT-TYPE 962 SYNTAX INTEGER { 963 normal (0), 964 alarm (1) 965 } 966 MAX-ACCESS read-only 967 STATUS current 968 DESCRIPTION 969 "The A Bus (primary loads) Contactor alarm. The contactor dropout voltage has been 970 reached and the contactor will release." 971 ::= { alarmWellknownAlarms 8 } 972 973alarmLVD2open OBJECT-TYPE 974 SYNTAX INTEGER { 975 normal (0), 976 alarm (1) 977 } 978 MAX-ACCESS read-only 979 STATUS current 980 DESCRIPTION 981 "The B Bus (secondary loads) Contactor alarm. The contactor dropout voltage has been 982 reached and the contactor will release." 983 ::= { alarmWellknownAlarms 9 } 984 985alarmLVD3open OBJECT-TYPE 986 SYNTAX INTEGER { 987 normal (0), 988 alarm (1) 989 } 990 MAX-ACCESS read-only 991 STATUS current 992 DESCRIPTION 993 "The C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been 994 reached and the contactor will release. 995 " 996 ::= { alarmWellknownAlarms 10 } 997 998alarmACmains OBJECT-TYPE 999 SYNTAX INTEGER { 1000 normal (0), 1001 alarm (1) 1002 } 1003 MAX-ACCESS read-only 1004 STATUS current 1005 DESCRIPTION 1006 "The AC voltage has dropped below critical level, 1007 or one or more AC input phases was lost." 1008 ::= { alarmWellknownAlarms 11 } 1009 1010alarmBatteryBreakerOpen OBJECT-TYPE 1011 SYNTAX INTEGER { 1012 normal (0), 1013 alarm (1) 1014 } 1015 MAX-ACCESS read-only 1016 STATUS current 1017 DESCRIPTION 1018 "Battery string disconnect breaker/fuse alarm" 1019 ::= { alarmWellknownAlarms 12 } 1020 1021alarmDistributionBreakerOpen OBJECT-TYPE 1022 SYNTAX INTEGER { 1023 normal (0), 1024 alarm (1) 1025 } 1026 MAX-ACCESS read-only 1027 STATUS current 1028 DESCRIPTION 1029 "The Load Distribution breaker/fuse alarm " 1030 ::= { alarmWellknownAlarms 13 } 1031 1032alarmMajorRectifier OBJECT-TYPE 1033 SYNTAX INTEGER { 1034 normal (0), 1035 alarm (1) 1036 } 1037 MAX-ACCESS read-only 1038 STATUS current 1039 DESCRIPTION 1040 "This is a 'multiple rectifiers have failed' alarm" 1041 ::= { alarmWellknownAlarms 14 } 1042 1043alarmMinorRectifier OBJECT-TYPE 1044 SYNTAX INTEGER { 1045 normal (0), 1046 alarm (1) 1047 } 1048 MAX-ACCESS read-only 1049 STATUS current 1050 DESCRIPTION 1051 "This is a 'one rectifier has failed' alarm" 1052 ::= { alarmWellknownAlarms 15 } 1053 1054alarmMajorBatteryMidpoint OBJECT-TYPE 1055 SYNTAX INTEGER { 1056 normal (0), 1057 alarm (1) 1058 } 1059 MAX-ACCESS read-only 1060 STATUS current 1061 DESCRIPTION 1062 "Battery Symmetry (midpoint) Delta Voltage is badly out of limits alarm" 1063 ::= { alarmWellknownAlarms 16 } 1064 1065alarmMinorBatteryMidpoint OBJECT-TYPE 1066 SYNTAX INTEGER { 1067 normal (0), 1068 alarm (1) 1069 } 1070 MAX-ACCESS read-only 1071 STATUS current 1072 DESCRIPTION 1073 "Battery Symmetry (midpoint) Delta Voltage out of limits alarm" 1074 ::= { alarmWellknownAlarms 17 } 1075 1076alarmBatteryLifeEnded OBJECT-TYPE 1077 SYNTAX INTEGER { 1078 normal (0), 1079 alarm (1) 1080 } 1081 MAX-ACCESS read-only 1082 STATUS current 1083 DESCRIPTION 1084 "The battery capacity has dropped below critical level. 1085 A battery test has measured the fully charged capacity to be too low, 1086 and thus probably the battery lifecycle to be near expired." 1087 ::= { alarmWellknownAlarms 18 } 1088 1089alarmBatteryTestmodeEntered OBJECT-TYPE 1090 SYNTAX INTEGER { 1091 normal (0), 1092 alarm (1) 1093 } 1094 MAX-ACCESS read-only 1095 STATUS current 1096 DESCRIPTION 1097 "The system has lowered the battery charge voltage in order to discharge the batteries 1098 to a predefinend level. When the criteria for stopping the battery testing is reached, the 1099 charge voltage is increased to commence normal charging." 1100 ::= { alarmWellknownAlarms 19 } 1101 1102alarmBatteryBoostmodeEntered OBJECT-TYPE 1103 SYNTAX INTEGER { 1104 normal (0), 1105 alarm (1) 1106 } 1107 MAX-ACCESS read-only 1108 STATUS current 1109 DESCRIPTION 1110 "The system has increased the battery charge voltage in order to equalize the 1111 battery cells charging. When the criteria for stopping the battery equalizing is reached, 1112 the charge voltage is lowered to commence normal charging." 1113 ::= { alarmWellknownAlarms 20 } 1114 1115alarmUserConfigurable1 OBJECT-TYPE 1116 SYNTAX INTEGER { 1117 normal (0), 1118 alarm (1) 1119 } 1120 MAX-ACCESS read-only 1121 STATUS current 1122 DESCRIPTION 1123 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1124 User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. " 1125 ::= { alarmWellknownAlarms 21 } 1126 1127alarmUserConfigurable2 OBJECT-TYPE 1128 SYNTAX INTEGER { 1129 normal (0), 1130 alarm (1) 1131 } 1132 MAX-ACCESS read-only 1133 STATUS current 1134 DESCRIPTION 1135 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1136 User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. " 1137 ::= { alarmWellknownAlarms 22 } 1138 1139alarmUserConfigurable3 OBJECT-TYPE 1140 SYNTAX INTEGER { 1141 normal (0), 1142 alarm (1) 1143 } 1144 MAX-ACCESS read-only 1145 STATUS current 1146 DESCRIPTION 1147 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1148 User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. " 1149 ::= { alarmWellknownAlarms 23 } 1150 1151alarmUserConfigurable4 OBJECT-TYPE 1152 SYNTAX INTEGER { 1153 normal (0), 1154 alarm (1) 1155 } 1156 MAX-ACCESS read-only 1157 STATUS current 1158 DESCRIPTION 1159 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1160 User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. " 1161 ::= { alarmWellknownAlarms 24 } 1162 1163alarmUserConfigurable5 OBJECT-TYPE 1164 SYNTAX INTEGER { 1165 normal (0), 1166 alarm (1) 1167 } 1168 MAX-ACCESS read-only 1169 STATUS current 1170 DESCRIPTION 1171 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1172 User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. " 1173 ::= { alarmWellknownAlarms 25 } 1174 1175alarmUserConfigurable6 OBJECT-TYPE 1176 SYNTAX INTEGER { 1177 normal (0), 1178 alarm (1) 1179 } 1180 MAX-ACCESS read-only 1181 STATUS current 1182 DESCRIPTION 1183 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1184 User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. " 1185 ::= { alarmWellknownAlarms 26 } 1186 1187alarmUserConfigurable7 OBJECT-TYPE 1188 SYNTAX INTEGER { 1189 normal (0), 1190 alarm (1) 1191 } 1192 MAX-ACCESS read-only 1193 STATUS current 1194 DESCRIPTION 1195 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1196 User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. " 1197 ::= { alarmWellknownAlarms 27 } 1198 1199alarmUserConfigurable8 OBJECT-TYPE 1200 SYNTAX INTEGER { 1201 normal (0), 1202 alarm (1) 1203 } 1204 MAX-ACCESS read-only 1205 STATUS current 1206 DESCRIPTION 1207 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1208 User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. " 1209 ::= { alarmWellknownAlarms 28 } 1210 1211alarmUserConfigurable9 OBJECT-TYPE 1212 SYNTAX INTEGER { 1213 normal (0), 1214 alarm (1) 1215 } 1216 MAX-ACCESS read-only 1217 STATUS current 1218 DESCRIPTION 1219 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1220 User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. " 1221 ::= { alarmWellknownAlarms 29 } 1222 1223alarmUserConfigurable10 OBJECT-TYPE 1224 SYNTAX INTEGER { 1225 normal (0), 1226 alarm (1) 1227 } 1228 MAX-ACCESS read-only 1229 STATUS current 1230 DESCRIPTION 1231 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1232 User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. " 1233 ::= { alarmWellknownAlarms 30 } 1234 1235alarmUserConfigurable11 OBJECT-TYPE 1236 SYNTAX INTEGER { 1237 normal (0), 1238 alarm (1) 1239 } 1240 MAX-ACCESS read-only 1241 STATUS current 1242 DESCRIPTION 1243 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1244 User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. " 1245 ::= { alarmWellknownAlarms 31 } 1246 1247alarmUserConfigurable12 OBJECT-TYPE 1248 SYNTAX INTEGER { 1249 normal (0), 1250 alarm (1) 1251 } 1252 MAX-ACCESS read-only 1253 STATUS current 1254 DESCRIPTION 1255 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1256 User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. " 1257 ::= { alarmWellknownAlarms 32 } 1258 1259alarmUserConfigurable13 OBJECT-TYPE 1260 SYNTAX INTEGER { 1261 normal (0), 1262 alarm (1) 1263 } 1264 MAX-ACCESS read-only 1265 STATUS current 1266 DESCRIPTION 1267 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1268 User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. " 1269 ::= { alarmWellknownAlarms 33 } 1270 1271alarmUserConfigurable14 OBJECT-TYPE 1272 SYNTAX INTEGER { 1273 normal (0), 1274 alarm (1) 1275 } 1276 MAX-ACCESS read-only 1277 STATUS current 1278 DESCRIPTION 1279 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1280 User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. " 1281 ::= { alarmWellknownAlarms 34 } 1282 1283dcSystemTraps NOTIFICATION-GROUP 1284 NOTIFICATIONS { alarmMajorHighBattVoltTrap, 1285 alarmMinorHighBattVoltTrap, 1286 alarmMajorLowBattVoltTrap, 1287 alarmMinorLowBattVoltTrap, 1288 alarmMajorBatteryHighTempTrap, 1289 alarmMinorBatteryHighTempTrap, 1290 alarmBatteryDisconnectOpenTrap, 1291 alarmLVD1openTrap, 1292 alarmLVD2openTrap, 1293 alarmLVD3openTrap, 1294 alarmACmainsTrap, 1295 alarmBatteryBreakerOpenTrap, 1296 alarmDistributionBreakerOpenTrap, 1297 alarmMajorRectifierTrap, 1298 alarmMinorRectifierTrap, 1299 alarmMajorBatteryMidpointTrap, 1300 alarmMinorBatteryMidpointTrap, 1301 alarmBatteryLifeEndedTrap, 1302 alarmBatteryTestmodeEnteredTrap, 1303 alarmBatteryBoostmodeEnteredTrap, 1304 alarmUserConfigurable1Trap, 1305 alarmUserConfigurable2Trap, 1306 alarmUserConfigurable3Trap, 1307 alarmUserConfigurable4Trap, 1308 alarmUserConfigurable5Trap, 1309 alarmUserConfigurable6Trap, 1310 alarmUserConfigurable7Trap, 1311 alarmUserConfigurable8Trap, 1312 alarmUserConfigurable9Trap, 1313 alarmUserConfigurable10Trap, 1314 alarmUserConfigurable11Trap, 1315 alarmUserConfigurable12Trap, 1316 alarmUserConfigurable13Trap, 1317 alarmUserConfigurable14Trap } 1318 STATUS current 1319 DESCRIPTION 1320 " This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. 1321 Each alarm condition is represented by a Alarm Condition Trap and an associated OFF 1322 Trap, which is optionally transmitted according to the state of OID systemSendOffTrap" 1323 ::= { eltekPlant 8 } 1324 1325 1326 1327 1328 1329alarmMajorHighBattVoltTrap NOTIFICATION-TYPE 1330 OBJECTS { alarmMajorHighBattVolt} 1331 STATUS current 1332 DESCRIPTION 1333 "The Very High Battery Voltage alarm" 1334 ::= { dcSystemTraps 1 } 1335 1336alarmMinorHighBattVoltTrap NOTIFICATION-TYPE 1337 OBJECTS { alarmMinorHighBattVolt} 1338 STATUS current 1339 DESCRIPTION 1340 "The High Battery Voltage alarm" 1341 ::= { dcSystemTraps 2 } 1342 1343alarmMajorLowBattVoltTrap NOTIFICATION-TYPE 1344 OBJECTS { alarmMajorLowBattVolt} 1345 STATUS current 1346 DESCRIPTION 1347 "The Very Low Battery Voltage Alarm" 1348 ::= { dcSystemTraps 3 } 1349 1350alarmMinorLowBattVoltTrap NOTIFICATION-TYPE 1351 OBJECTS { alarmMinorLowBattVolt} 1352 STATUS current 1353 DESCRIPTION 1354 "The Low Battery Voltage Alarm" 1355 ::= { dcSystemTraps 4 } 1356 1357alarmMajorBatteryHighTempTrap NOTIFICATION-TYPE 1358 OBJECTS { alarmMajorBatteryHighTemp} 1359 STATUS current 1360 DESCRIPTION 1361 "High Battery temperature alarm or 1362 Temperature Compensation circuit / probe failure alarm" 1363 ::= { dcSystemTraps 5 } 1364 1365alarmMinorBatteryHighTempTrap NOTIFICATION-TYPE 1366 OBJECTS { alarmMinorBatteryHighTemp} 1367 STATUS current 1368 DESCRIPTION 1369 "High Battery temperature alarm" 1370 ::= { dcSystemTraps 6 } 1371 1372alarmBatteryDisconnectOpenTrap NOTIFICATION-TYPE 1373 OBJECTS { alarmBatteryDisconnectOpen} 1374 STATUS current 1375 DESCRIPTION 1376 "The Battery Disconnect Contactor alarm" 1377 ::= { dcSystemTraps 7 } 1378 1379alarmLVD1openTrap NOTIFICATION-TYPE 1380 OBJECTS { alarmLVD1open} 1381 STATUS current 1382 DESCRIPTION 1383 "The A Bus (primary loads) Contactor is open alarm" 1384 ::= { dcSystemTraps 8 } 1385 1386alarmLVD2openTrap NOTIFICATION-TYPE 1387 OBJECTS { alarmLVD2open} 1388 STATUS current 1389 DESCRIPTION 1390 "The B Bus (secondary loads) Contactor is open alarm" 1391 ::= { dcSystemTraps 9 } 1392 1393alarmLVD3openTrap NOTIFICATION-TYPE 1394 OBJECTS { alarmLVD3open} 1395 STATUS current 1396 DESCRIPTION 1397 "The C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been 1398 reached and the contactor is released. 1399 " 1400 ::= { dcSystemTraps 10 } 1401 1402alarmACmainsTrap NOTIFICATION-TYPE 1403 OBJECTS { alarmACmains} 1404 STATUS current 1405 DESCRIPTION 1406 "The AC voltage has dropped below critical level, 1407 or one or more AC input phases was lost." 1408 ::= { dcSystemTraps 11 } 1409 1410alarmBatteryBreakerOpenTrap NOTIFICATION-TYPE 1411 OBJECTS { alarmBatteryBreakerOpen} 1412 STATUS current 1413 DESCRIPTION 1414 "Battery string disconnect breaker/fuse alarm" 1415 ::= { dcSystemTraps 12 } 1416 1417alarmDistributionBreakerOpenTrap NOTIFICATION-TYPE 1418 OBJECTS { alarmDistributionBreakerOpen} 1419 STATUS current 1420 DESCRIPTION 1421 "The Load Distribution breaker/fuse alarm" 1422 ::= { dcSystemTraps 13 } 1423 1424alarmMajorRectifierTrap NOTIFICATION-TYPE 1425 OBJECTS { alarmMajorRectifier} 1426 STATUS current 1427 DESCRIPTION 1428 "This is a 'multiple rectifiers have failed' alarm" 1429 ::= { dcSystemTraps 14 } 1430 1431alarmMinorRectifierTrap NOTIFICATION-TYPE 1432 OBJECTS { alarmMinorRectifier} 1433 STATUS current 1434 DESCRIPTION 1435 "This is a 'one rectifier has failed' alarm" 1436 ::= { dcSystemTraps 15 } 1437 1438alarmMajorBatteryMidpointTrap NOTIFICATION-TYPE 1439 OBJECTS { alarmMajorBatteryMidpoint} 1440 STATUS current 1441 DESCRIPTION 1442 "Battery Symmetry (midpoint) Delta Voltage out of 'major fault' limits alarm" 1443 ::= { dcSystemTraps 16 } 1444 1445alarmMinorBatteryMidpointTrap NOTIFICATION-TYPE 1446 OBJECTS { alarmMinorBatteryMidpoint} 1447 STATUS current 1448 DESCRIPTION 1449 "Battery Symmetry (midpoint) Delta Voltage out of limits alarm" 1450 ::= { dcSystemTraps 17 } 1451 1452alarmBatteryLifeEndedTrap NOTIFICATION-TYPE 1453 OBJECTS { alarmBatteryLifeEnded} 1454 STATUS current 1455 DESCRIPTION 1456 "The battery capacity has dropped below critical level. 1457 A battery test has measured the fully charged capacity to be too low, 1458 and thus probably the battery lifecycle to be near expired." 1459 ::= { dcSystemTraps 18 } 1460 1461alarmBatteryTestmodeEnteredTrap NOTIFICATION-TYPE 1462 OBJECTS { alarmBatteryTestmodeEntered} 1463 STATUS current 1464 DESCRIPTION 1465 "The system has lowered the battery charge voltage in order to discharge the batteries 1466 to a predefinend level. When the criteria for stopping the battery testing is reached, the 1467 charge voltage is increased to commence normal charging." 1468 ::= { dcSystemTraps 19 } 1469 1470alarmBatteryBoostmodeEnteredTrap NOTIFICATION-TYPE 1471 OBJECTS { alarmBatteryBoostmodeEntered} 1472 STATUS current 1473 DESCRIPTION 1474 "The system has increased the battery charge voltage in order to equalize the 1475 battery cells charging. When the criteria for stopping the battery equalizing is reached, 1476 the charge voltage is lowered to commence normal charging." 1477 ::= { dcSystemTraps 20 } 1478 1479alarmUserConfigurable1Trap NOTIFICATION-TYPE 1480 OBJECTS { alarmUserConfigurable1} 1481 STATUS current 1482 DESCRIPTION 1483 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1484 User configurable alarms will on some systems have text attached to the traps 1485 that explains the purpose of the alarm. " 1486 ::= { dcSystemTraps 21 } 1487 1488alarmUserConfigurable2Trap NOTIFICATION-TYPE 1489 OBJECTS { alarmUserConfigurable2} 1490 STATUS current 1491 DESCRIPTION 1492 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1493 User configurable alarms will on some systems have text attached to the traps 1494 that explains the purpose of the alarm. " 1495 ::= { dcSystemTraps 22 } 1496 1497alarmUserConfigurable3Trap NOTIFICATION-TYPE 1498 OBJECTS { alarmUserConfigurable3} 1499 STATUS current 1500 DESCRIPTION 1501 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1502 User configurable alarms will on some systems have text attached to the traps 1503 that explains the purpose of the alarm. " 1504 ::= { dcSystemTraps 23 } 1505 1506alarmUserConfigurable4Trap NOTIFICATION-TYPE 1507 OBJECTS { alarmUserConfigurable4} 1508 STATUS current 1509 DESCRIPTION 1510 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1511 User configurable alarms will on some systems have text attached to the traps 1512 that explains the purpose of the alarm. " 1513 ::= { dcSystemTraps 24 } 1514 1515alarmUserConfigurable5Trap NOTIFICATION-TYPE 1516 OBJECTS { alarmUserConfigurable5} 1517 STATUS current 1518 DESCRIPTION 1519 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1520 User configurable alarms will on some systems have text attached to the traps 1521 that explains the purpose of the alarm. " 1522 ::= { dcSystemTraps 25 } 1523 1524alarmUserConfigurable6Trap NOTIFICATION-TYPE 1525 OBJECTS { alarmUserConfigurable6} 1526 STATUS current 1527 DESCRIPTION 1528 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1529 User configurable alarms will on some systems have text attached to the traps 1530 that explains the purpose of the alarm. " 1531 ::= { dcSystemTraps 26 } 1532 1533alarmUserConfigurable7Trap NOTIFICATION-TYPE 1534 OBJECTS { alarmUserConfigurable7} 1535 STATUS current 1536 DESCRIPTION 1537 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1538 User configurable alarms will on some systems have text attached to the traps 1539 that explains the purpose of the alarm. " 1540 ::= { dcSystemTraps 27 } 1541 1542alarmUserConfigurable8Trap NOTIFICATION-TYPE 1543 OBJECTS { alarmUserConfigurable8} 1544 STATUS current 1545 DESCRIPTION 1546 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1547 User configurable alarms will on some systems have text attached to the traps 1548 that explains the purpose of the alarm. " 1549 ::= { dcSystemTraps 28 } 1550 1551alarmUserConfigurable9Trap NOTIFICATION-TYPE 1552 OBJECTS { alarmUserConfigurable9} 1553 STATUS current 1554 DESCRIPTION 1555 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1556 User configurable alarms will on some systems have text attached to the traps 1557 that explains the purpose of the alarm. " 1558 ::= { dcSystemTraps 29 } 1559 1560alarmUserConfigurable10Trap NOTIFICATION-TYPE 1561 OBJECTS { alarmUserConfigurable10} 1562 STATUS current 1563 DESCRIPTION 1564 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1565 User configurable alarms will on some systems have text attached to the traps 1566 that explains the purpose of the alarm. " 1567 ::= { dcSystemTraps 30 } 1568 1569alarmUserConfigurable11Trap NOTIFICATION-TYPE 1570 OBJECTS { alarmUserConfigurable11} 1571 STATUS current 1572 DESCRIPTION 1573 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1574 User configurable alarms will on some systems have text attached to the traps 1575 that explains the purpose of the alarm. " 1576 ::= { dcSystemTraps 31 } 1577 1578alarmUserConfigurable12Trap NOTIFICATION-TYPE 1579 OBJECTS { alarmUserConfigurable12} 1580 STATUS current 1581 DESCRIPTION 1582 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1583 User configurable alarms will on some systems have text attached to the traps 1584 that explains the purpose of the alarm. " 1585 ::= { dcSystemTraps 32 } 1586 1587alarmUserConfigurable13Trap NOTIFICATION-TYPE 1588 OBJECTS { alarmUserConfigurable13} 1589 STATUS current 1590 DESCRIPTION 1591 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1592 User configurable alarms will on some systems have text attached to the traps 1593 that explains the purpose of the alarm. " 1594 ::= { dcSystemTraps 33 } 1595 1596alarmUserConfigurable14Trap NOTIFICATION-TYPE 1597 OBJECTS { alarmUserConfigurable14} 1598 STATUS current 1599 DESCRIPTION 1600 "Generic alarm linked to user specified alarms. These have no specific name in the MIB. 1601 User configurable alarms will on some systems have text attached to the traps 1602 that explains the purpose of the alarm. " 1603 ::= { dcSystemTraps 34 } 1604 1605 1606 1607 1608END 1609 1610 1611-- This MIB was created using NuDesign Team's Visual MIBuilder (Ver 4.4). 1612 1613