1
2-- Eltek OEM MIB for Nextel Digital Power plant designs
3
4ELTEK_GENERIC-MIB DEFINITIONS ::= BEGIN
5
6IMPORTS
7	NOTIFICATION-TYPE, OBJECT-TYPE, MODULE-IDENTITY,
8	mib-2, enterprises, Integer32
9		FROM SNMPv2-SMI
10	NOTIFICATION-GROUP
11		FROM SNMPv2-CONF
12	DisplayString
13		FROM SNMPv2-TC
14	eltek
15		FROM ELTEK_COMMON-MIB;
16
17
18-- Aeongold	branch will be 1
19-- AL175		branch will be 2
20-- AL6000		branch will be 3
21-- Webpower proto	branch will be 4
22-- ENEXUS		branch will be 5
23-- Nextel Smartpack	branch will be 6
24-- ELTEK Common     branch will be 7
25
26eltekPlant           OBJECT IDENTIFIER ::= { eltek 7 }
27
28-- This branch contains OIDs for configuration of the Smartpack Control System's
29-- basic data and settings
30
31controlSystem        OBJECT IDENTIFIER ::= { eltekPlant 1 }
32systemTime           OBJECT IDENTIFIER ::= { controlSystem 1 }
33
34-- This branch contains OIDs for configuration of the DC Power System's
35-- basic factory data and user's installation settings
36
37dcSystem             OBJECT IDENTIFIER ::= { eltekPlant 2 }
38dcPlant              OBJECT IDENTIFIER ::= { dcSystem 1 }
39
40-- This branch contains OIDs for configuration of the DC Power System's
41-- installation and location settings
42
43systemSiteInfo       OBJECT IDENTIFIER ::= { dcPlant 3 }
44
45-- This branch contains OIDs for configuration of the DC Power System's
46-- Battery charging and protection related settings
47
48battery              OBJECT IDENTIFIER ::= { eltekPlant 3 }
49
50-- This branch contains OIDs for configuration of the DC Power System's
51-- Battery Disconnect Contactor  / Emergency Disconnect related settings
52
53batteryLVD           OBJECT IDENTIFIER ::= { battery 17 }
54
55-- This branch contains OIDs for configuration of the DC Power System's
56-- Battery Symmetry Monitor related settings
57
58batteryMidpoint      OBJECT IDENTIFIER ::= { battery 18 }
59
60-- This branch contains OIDs related to the DC Load Distribution equipment
61
62loadDistribution     OBJECT IDENTIFIER ::= { eltekPlant 4 }
63
64-- This branch contains OIDs related to the Load Disconnect / Load Shedding equipment
65
66loadDistributionLVDStatus  OBJECT IDENTIFIER ::= { loadDistribution 3 }
67
68-- This branch contains OIDs related to the Flatpack 2 rectifier parameters
69
70rectifier            OBJECT IDENTIFIER ::= { eltekPlant 5 }
71
72-- This branch contains OIDs for polling of the Flatpack 2 Rectifier status settings
73
74rectifierStatus      OBJECT IDENTIFIER ::= { rectifier 5 }
75acDistribution       OBJECT IDENTIFIER ::= { eltekPlant 6 }
76
77-- This branch contains Alarms and Events that are mappable to alarm relay positions.
78-- Also duplicated as Traps
79
80alarmGroup           OBJECT IDENTIFIER ::= { eltekPlant 7 }
81
82-- Common alarm types: (12) as specified by Nextel as relay outputs,
83-- others available for inclusion to Plant summation alarms
84
85alarmWellknownAlarms  OBJECT IDENTIFIER ::= { alarmGroup 1 }
86
87systemTimeTime  OBJECT-TYPE
88	SYNTAX     DisplayString (SIZE(0..255))
89	MAX-ACCESS read-only
90	STATUS     current
91	DESCRIPTION
92		"The system date and time. Used for event timestamps and logging"
93	::= { systemTime 1 }
94
95systemInfoRefresh  OBJECT-TYPE
96	SYNTAX     INTEGER {
97		pushbutton (0),
98		refreshdata (1)
99	}
100	MAX-ACCESS read-write
101	STATUS     current
102	DESCRIPTION
103		"This object will re-initialize the agent, updating MIB data values."
104	::= { controlSystem 2 }
105
106systemTrapRepeatRate  OBJECT-TYPE
107	SYNTAX     Integer32 (0..10)
108	MAX-ACCESS read-write
109	STATUS     current
110	DESCRIPTION
111		"This object sets the repeat rate of any active traps, in seconds.
112		Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event."
113	::= { controlSystem 3 }
114
115systemSendOffTrap  OBJECT-TYPE
116	SYNTAX     INTEGER {
117		off (0),
118		on (1)
119	}
120	MAX-ACCESS read-write
121	STATUS     current
122	DESCRIPTION
123		"A separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1.
124		Entering 0 (zero) will prevent OFF traps from being transmitted."
125	::= { controlSystem 4 }
126
127systemSiteInfoCustomer  OBJECT-TYPE
128	SYNTAX     DisplayString (SIZE(0..32))
129	MAX-ACCESS read-only
130	STATUS     current
131	DESCRIPTION
132		"The Customer name (as stored in the Smartpack Control Unit)"
133	::= { systemSiteInfo 1 }
134
135systemSiteInfoLocation  OBJECT-TYPE
136	SYNTAX     DisplayString (SIZE(0..32))
137	MAX-ACCESS read-only
138	STATUS     current
139	DESCRIPTION
140		"The system/site Location details (as stored in the Smartpack Control Unit)."
141	::= { systemSiteInfo 2 }
142
143systemSiteInfoMessage1  OBJECT-TYPE
144	SYNTAX     DisplayString (SIZE(0..32))
145	MAX-ACCESS read-only
146	STATUS     current
147	DESCRIPTION
148		"The system/site Info Message record #1 (as stored in the Smartpack Control Unit). 31 Bytes."
149	::= { systemSiteInfo 3 }
150
151systemSiteInfoMessage2  OBJECT-TYPE
152	SYNTAX     DisplayString (SIZE(0..32))
153	MAX-ACCESS read-only
154	STATUS     current
155	DESCRIPTION
156		"The system/site Info Message record #2 (as stored in the Smartpack Control Unit). 31 Bytes."
157	::= { systemSiteInfo 4 }
158
159systemSiteInfoInstalledDate  OBJECT-TYPE
160	SYNTAX     DisplayString (SIZE(0..16))
161	MAX-ACCESS read-only
162	STATUS     current
163	DESCRIPTION
164		"The system's Installed Date text string (as stored in the Smartpack Control Unit) 16bytes."
165	::= { systemSiteInfo 5 }
166
167systemSiteInfoControllerType  OBJECT-TYPE
168	SYNTAX     INTEGER {
169		al175 (0),
170		al4000 (1),
171		al6000 (2),
172		enexus (3)
173	}
174	MAX-ACCESS read-only
175	STATUS     current
176	DESCRIPTION
177		"The system Controller Module currently connected.
178		 AL175/MCU=0; AEON Gold=1; AL6000=2; Smartpack=3"
179	::= { systemSiteInfo 6 }
180
181systemSiteInfoSystemSeriaNum  OBJECT-TYPE
182	SYNTAX     DisplayString (SIZE(0..16))
183	MAX-ACCESS read-only
184	STATUS     current
185	DESCRIPTION
186		"The serial number for the complete system"
187	::= { systemSiteInfo 7 }
188
189systemSiteInfoControllerSeriaNum  OBJECT-TYPE
190	SYNTAX     DisplayString (SIZE(0..16))
191	MAX-ACCESS read-only
192	STATUS     current
193	DESCRIPTION
194		"The serial number for the system controller"
195	::= { systemSiteInfo 8 }
196
197systemNominalVoltage  OBJECT-TYPE
198	SYNTAX     INTEGER {
199		prs48v (0),
200		prs24v (1),
201		prs12v (2),
202		prs26v (3),
203		prs60v (4)
204	}
205	MAX-ACCESS read-only
206	STATUS     current
207	DESCRIPTION
208		"The nominal voltage rating. 12V/24V/48V/60V systems
209		 0=48V
210		 1=24V
211		 2=12V
212		 3=26V
213		 4=60V"
214	::= { dcPlant 4 }
215
216systemOperationalStatus  OBJECT-TYPE
217	SYNTAX     INTEGER {
218		floatvoltreg (0),
219		floattempcomp (1),
220		batteryboost (2),
221		batterytest (3)
222	}
223	MAX-ACCESS read-only
224	STATUS     current
225	DESCRIPTION
226		"A summary status showing if the system is testing, boosting, floating etc.
227		 0=Float, voltage regulated
228		 1=Float, temperature comp. regulated;
229		 2=equalize
230		 3=battery test"
231	::= { dcSystem 2 }
232
233batteryName  OBJECT-TYPE
234	SYNTAX     DisplayString (SIZE(0..16))
235	MAX-ACCESS read-only
236	STATUS     current
237	DESCRIPTION
238		"A descriptive name of the battery installed in the system"
239	::= { battery 1 }
240
241batteryVoltage  OBJECT-TYPE
242	SYNTAX     Integer32 (0..7500)
243	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
244	MAX-ACCESS read-only
245	STATUS     current
246	DESCRIPTION
247		"The measured battery voltage."
248	::= { battery 2 }
249
250batteryCurrent  OBJECT-TYPE
251	SYNTAX     Integer32
252	UNITS 	"Amperes; i.e. 20 = 20 Amperes"
253	MAX-ACCESS read-only
254	STATUS     current
255	DESCRIPTION
256		"The measured battery current."
257	::= { battery 3 }
258
259batteryTemp  OBJECT-TYPE
260	SYNTAX     Integer32 (0..9999)
261	UNITS 	"1/10 Deg. C; i.e. 250 = 25.0 Deg. C."
262	MAX-ACCESS read-only
263	STATUS     current
264	DESCRIPTION
265		"The battery temperature "
266	::= { battery 4 }
267
268batteryBreakerStatus  OBJECT-TYPE
269	SYNTAX     INTEGER {
270		closed (0),
271		open (1)
272	}
273	MAX-ACCESS read-only
274	STATUS     current
275	DESCRIPTION
276		"The state of the battery fuse/breaker can be either closed(0) or open(1) "
277	::= { battery 5 }
278
279batteryChargeCurrentLimitCtrl  OBJECT-TYPE
280	SYNTAX     INTEGER {
281		deactivate (0),
282		activate (1)
283	}
284	MAX-ACCESS read-write
285	STATUS     current
286	DESCRIPTION
287		"Control field for the battery charge limitation feature; 0=inactive, 1=active."
288	::= { battery 6 }
289
290batteryChargeCurrentLimitValue  OBJECT-TYPE
291	SYNTAX     Integer32 (0..2100)
292	UNITS 	"Amperes; i.e. 20 = 20 Amperes"
293	MAX-ACCESS read-write
294	STATUS     current
295	DESCRIPTION
296		"Battery charging current limit value"
297	::= { battery 7 }
298
299batteryTempCompEnable  OBJECT-TYPE
300	SYNTAX     INTEGER {
301		disable (0),
302		enable (1)
303	}
304	MAX-ACCESS read-write
305	STATUS     current
306	DESCRIPTION
307		"Enable (0) or Disable (1) Battery Temperature Compensated output regulation mode"
308	::= { battery 8 }
309
310batteryFloatVoltConfig  OBJECT-TYPE
311	SYNTAX     Integer32 (4300..6000)
312	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
313	MAX-ACCESS read-write
314	STATUS     current
315	DESCRIPTION
316		"The Voltage at which the DC System float charges."
317	::= { battery 9 }
318
319batteryEqualizeVoltConfig  OBJECT-TYPE
320	SYNTAX     Integer32 (4300..6000)
321	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
322	MAX-ACCESS read-write
323	STATUS     current
324	DESCRIPTION
325		"The Voltage at which the DC System boost charges the batteries."
326	::= { battery 10 }
327
328batteryHighMajorAlarmVoltageConfig  OBJECT-TYPE
329	SYNTAX     Integer32
330	MAX-ACCESS read-write
331	STATUS     current
332	DESCRIPTION
333		"The High Battery Voltage alarm limit set voltage"
334	::= { battery 11 }
335
336batteryHighMinorAlarmVoltageConfig  OBJECT-TYPE
337	SYNTAX     Integer32
338	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
339	MAX-ACCESS read-write
340	STATUS     current
341	DESCRIPTION
342		"The High Battery Voltage alarm limit set voltage"
343	::= { battery 12 }
344
345batteryLowMajorAlarmVoltageConfig  OBJECT-TYPE
346	SYNTAX     Integer32
347	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
348	MAX-ACCESS read-write
349	STATUS     current
350	DESCRIPTION
351		"The Low Battery Voltage Alarm limit set voltage"
352	::= { battery 13 }
353
354-- This alarm may be used to warn of impending Low Voltage Battery Disconnect operation
355
356batteryLowMinorAlarmVoltageConfig  OBJECT-TYPE
357	SYNTAX     Integer32
358	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
359	MAX-ACCESS read-write
360	STATUS     current
361	DESCRIPTION
362		"The Very Low Battery Voltage Alarm limit set voltage"
363	::= { battery 14 }
364
365batteryStartManualTest  OBJECT-TYPE
366	SYNTAX     INTEGER {
367		pushbutton (0),
368		starttest (1),
369		stoptest (2)
370	}
371	MAX-ACCESS read-write
372	STATUS     current
373	DESCRIPTION
374		"This pushbutton will start a manual battery test if otherwise the system allows it."
375	::= { battery 15 }
376
377batteryStartManualBoost  OBJECT-TYPE
378	SYNTAX     INTEGER {
379		pushbutton (0),
380		startboost (1),
381		stopboost (2)
382	}
383	MAX-ACCESS read-write
384	STATUS     current
385	DESCRIPTION
386		"This pushbutton will start a manual battery boost if otherwise the system allows it."
387	::= { battery 16 }
388
389batteryLVDStatus  OBJECT-TYPE
390	SYNTAX     INTEGER {
391		connect (0),
392		disconnect (1),
393		disable (2)
394	}
395	MAX-ACCESS read-only
396	STATUS     current
397	DESCRIPTION
398		"Contactor is closed(0) or open(1) "
399	::= { batteryLVD 1 }
400
401batteryLVDDisconnectVoltage  OBJECT-TYPE
402	SYNTAX     Integer32 (0..7200)
403	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
404	MAX-ACCESS read-write
405	STATUS     current
406	DESCRIPTION
407		"The Contactor Disconnect Voltage"
408	::= { batteryLVD 2 }
409
410batteryLVDConnectVoltage  OBJECT-TYPE
411	SYNTAX     Integer32 (0..7200)
412	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
413	MAX-ACCESS read-write
414	STATUS     current
415	DESCRIPTION
416		"The Contactor Reconnect Voltage"
417	::= { batteryLVD 3 }
418
419-- This setpoint / value is common for all battery strings monitored
420
421batteryMidpointDeltaLimitVoltage  OBJECT-TYPE
422	SYNTAX     Integer32
423	UNITS 	"1/100 Volt; i.e. 25 = 2.50V"
424	MAX-ACCESS read-write
425	STATUS     current
426	DESCRIPTION
427		"The allowable deviation of the midpoint battery voltage from the theoretical.
428		 Exceeding this value in either direction (+/-) causes an alarm state"
429	::= { batteryMidpoint 1 }
430
431batteryMidpointIndex  OBJECT-TYPE
432	SYNTAX     Integer32 (1..8)
433	MAX-ACCESS read-only
434	STATUS     current
435	DESCRIPTION
436		"An index of Battery Strings, for the batteryMidpointControlTable
437		 and batteryMidpointStatusTable arrays "
438	::= { batteryMidpoint 2 }
439
440batteryMidpointControlTable  OBJECT-TYPE
441	SYNTAX SEQUENCE OF BatteryMidpointControlEntry
442	MAX-ACCESS not-accessible
443	STATUS     current
444	DESCRIPTION
445		"A table of settings related to Battery Symmetry (midpoint) Monitoring"
446	::= { batteryMidpoint 3 }
447
448batteryMidpointControlEntry  OBJECT-TYPE
449	SYNTAX 	BatteryMidpointControlEntry
450	MAX-ACCESS not-accessible
451	STATUS     current
452	DESCRIPTION
453		"Settings related to Battery Symmetry (midpoint) Monitoring, corresponding
454		 to the batteryMidpointIndex value"
455	INDEX { batteryMidpointIndex }
456	::= { batteryMidpointControlTable 1 }
457
458BatteryMidpointControlEntry ::= SEQUENCE {
459	midpointEnableID
460		Integer32,
461	midpointEnable
462		INTEGER
463}
464
465midpointEnableID  OBJECT-TYPE
466	SYNTAX     Integer32 (1..8)
467	MAX-ACCESS read-only
468	STATUS     current
469	DESCRIPTION
470		"The rectifier ID number of the rectifier record."
471	::= { batteryMidpointControlEntry 1 }
472
473midpointEnable  OBJECT-TYPE
474	SYNTAX     INTEGER {
475		disable (0),
476		enable (1)
477	}
478	MAX-ACCESS read-write
479	STATUS     current
480	DESCRIPTION
481		"Enable (1) or Disable (0) the Battery Monitor channel which corresponds
482		 to the batteryMidpointIndex value"
483	::= { batteryMidpointControlEntry 2 }
484
485batteryMidpointStatusTable  OBJECT-TYPE
486	SYNTAX SEQUENCE OF BatteryMidpointStatusEntry
487	MAX-ACCESS not-accessible
488	STATUS     current
489	DESCRIPTION
490		"A table of values and/or measurements related to Battery Symmetry (midpoint) Monitoring"
491	::= { batteryMidpoint 4 }
492
493batteryMidpointStatusEntry  OBJECT-TYPE
494	SYNTAX 	BatteryMidpointStatusEntry
495	MAX-ACCESS not-accessible
496	STATUS     current
497	DESCRIPTION
498		"Values related to Battery Symmetry (midpoint) Monitoring, corresponding
499		 to the batteryMidpointIndex value"
500	INDEX { batteryMidpointIndex }
501	::= { batteryMidpointStatusTable 1 }
502
503BatteryMidpointStatusEntry ::= SEQUENCE {
504	midpointStatusID
505		Integer32,
506	midpointStatus
507		INTEGER,
508	midpointDeltaVoltage
509		Integer32
510}
511
512midpointStatusID  OBJECT-TYPE
513	SYNTAX     Integer32 (1..8)
514	MAX-ACCESS read-only
515	STATUS     current
516	DESCRIPTION
517		"The rectifier ID number of the rectifier record."
518	::= { batteryMidpointStatusEntry 1 }
519
520midpointStatus  OBJECT-TYPE
521	SYNTAX     INTEGER {
522		ok (0),
523		alarm (1),
524		disable (2)
525	}
526	MAX-ACCESS read-only
527	STATUS     current
528	DESCRIPTION
529		"Status (0=Normal; 1=Alarm) of the Battery Monitor channel which corresponds
530		 to the batteryMidpointIndex value"
531	::= { batteryMidpointStatusEntry 2 }
532
533midpointDeltaVoltage  OBJECT-TYPE
534	SYNTAX     Integer32
535	UNITS 	"1/100 Volt; i.e. 25 = 2.5V."
536	MAX-ACCESS read-only
537	STATUS     current
538	DESCRIPTION
539		"The measured battery voltage deviation from midpoint of the Battery Monitor channel
540		 which corresponds to the batteryMidpointIndex value."
541	::= { batteryMidpointStatusEntry 3 }
542
543loadDistributionCurrent  OBJECT-TYPE
544	SYNTAX     Integer32
545	UNITS 	"Amperes; i.e. 20 = 20 Amperes"
546	MAX-ACCESS read-only
547	STATUS     current
548	DESCRIPTION
549		"The total load current"
550	::= { loadDistribution 1 }
551
552loadDistributionBreakerStatus  OBJECT-TYPE
553	SYNTAX     INTEGER {
554		closed (0),
555		open (1)
556	}
557	MAX-ACCESS read-only
558	STATUS     current
559	DESCRIPTION
560		"The state of the load fuse/breaker can be either closed(0) or open(1) "
561	::= { loadDistribution 2 }
562
563loadLVD1EnableStatus  OBJECT-TYPE
564	SYNTAX     INTEGER {
565		disabled (0),
566		enabled (1)
567	}
568	MAX-ACCESS read-only
569	STATUS     current
570	DESCRIPTION
571		"The status of contactors configuration. 'enabled' means that the contactor is i n use. 'disabled' means that the contactor is disconfigured and not in use."
572	::= { loadDistributionLVDStatus 1 }
573
574loadLVD1Status  OBJECT-TYPE
575	SYNTAX     INTEGER {
576		connect (0),
577		disconnect (1),
578		disable (2)
579	}
580	MAX-ACCESS read-only
581	STATUS     current
582	DESCRIPTION
583		"The A Bus (primary loads) Contactor is closed(0) or open(1) "
584	::= { loadDistributionLVDStatus 2 }
585
586loadLVD1ConnectVoltage  OBJECT-TYPE
587	SYNTAX     Integer32 (0..7200)
588	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
589	MAX-ACCESS read-write
590	STATUS     current
591	DESCRIPTION
592		"The A Bus (primary loads) Contactor Connect Voltage"
593	::= { loadDistributionLVDStatus 3 }
594
595loadLVD1DisconnectVoltage  OBJECT-TYPE
596	SYNTAX     Integer32 (0..7200)
597	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
598	MAX-ACCESS read-write
599	STATUS     current
600	DESCRIPTION
601		"The A Bus (primary loads) Contactor Disconnect Voltage"
602	::= { loadDistributionLVDStatus 4 }
603
604loadLVD2EnableStatus  OBJECT-TYPE
605	SYNTAX     INTEGER {
606		disabled (0),
607		enabled (1)
608	}
609	MAX-ACCESS read-only
610	STATUS     current
611	DESCRIPTION
612		"The status of contactors configuration. 'enabled' means that the contactor is i n use.
613		'disabled' means that the contactor is disconfigured and not in use."
614	::= { loadDistributionLVDStatus 5 }
615
616loadLVD2Status  OBJECT-TYPE
617	SYNTAX     INTEGER {
618		connect (0),
619		disconnect (1),
620		disable (2)
621	}
622	MAX-ACCESS read-only
623	STATUS     current
624	DESCRIPTION
625		"The B Bus (secondary loads) Contactor is closed(0) or open(1) "
626	::= { loadDistributionLVDStatus 6 }
627
628loadLVD2ConnectVoltage  OBJECT-TYPE
629	SYNTAX     Integer32 (0..7200)
630	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
631	MAX-ACCESS read-write
632	STATUS     current
633	DESCRIPTION
634		"The B Bus (secondary loads) Contactor Connect Voltage"
635	::= { loadDistributionLVDStatus 7 }
636
637loadLVD2DisconnectVoltage  OBJECT-TYPE
638	SYNTAX     Integer32 (0..7200)
639	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
640	MAX-ACCESS read-write
641	STATUS     current
642	DESCRIPTION
643		"The B Bus (secondary loads) Contactor Disconnect Voltage"
644	::= { loadDistributionLVDStatus 8 }
645
646loadLVD3EnableStatus  OBJECT-TYPE
647	SYNTAX     INTEGER {
648		disabled (0),
649		enabled (1)
650	}
651	MAX-ACCESS read-only
652	STATUS     current
653	DESCRIPTION
654		"The status of contactors configuration. 'enabled' means that the contactor is i n use.
655		'disabled' means that the contactor is disconfigured and not in use."
656	::= { loadDistributionLVDStatus 9 }
657
658loadLVD3Status  OBJECT-TYPE
659	SYNTAX     INTEGER {
660		connect (0),
661		disconnect (1),
662		disable (2)
663	}
664	MAX-ACCESS read-only
665	STATUS     current
666	DESCRIPTION
667		"The C Bus (critical loads) Contactor is closed(0) or open(1) "
668	::= { loadDistributionLVDStatus 10 }
669
670loadLVD3ConnectVoltage  OBJECT-TYPE
671	SYNTAX     Integer32 (0..7200)
672	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
673	MAX-ACCESS read-write
674	STATUS     current
675	DESCRIPTION
676		"The C Bus (critical loads) Contactor Connect Voltage"
677	::= { loadDistributionLVDStatus 11 }
678
679loadLVD3DisconnectVoltage  OBJECT-TYPE
680	SYNTAX     Integer32 (0..7200)
681	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
682	MAX-ACCESS read-write
683	STATUS     current
684	DESCRIPTION
685		"The C Bus (critical loads) Contactor Disconnect Voltage"
686	::= { loadDistributionLVDStatus 12 }
687
688rectifierInstalledRectifiers  OBJECT-TYPE
689	SYNTAX     Integer32 (1..101)
690	MAX-ACCESS read-only
691	STATUS     current
692	DESCRIPTION
693		"The installed number of rectifiers for this DC Power System."
694	::= { rectifier 1 }
695
696rectifierRectifiersActive  OBJECT-TYPE
697	SYNTAX     Integer32 (1..101)
698	MAX-ACCESS read-only
699	STATUS     current
700	DESCRIPTION
701		"The actual number of active rectifiers in this DC Power System."
702	::= { rectifier 2 }
703
704rectifierTotalCurrent  OBJECT-TYPE
705	SYNTAX     Integer32
706	UNITS 	"Amperes; i.e. 20 = 20 Amperes"
707	MAX-ACCESS read-only
708	STATUS     current
709	DESCRIPTION
710		"The DC system's total available current"
711	::= { rectifier 3 }
712
713rectifierUtilization  OBJECT-TYPE
714	SYNTAX     Integer32 (0..100)
715	MAX-ACCESS read-only
716	STATUS     current
717	DESCRIPTION
718		"Utilization in % of available rectifier capacity"
719	::= { rectifier 4 }
720
721rectifierStatusNoIndex  OBJECT-TYPE
722	SYNTAX     Integer32 (1..20)
723	MAX-ACCESS read-write
724	STATUS     current
725	DESCRIPTION
726		"A starting index for the rectifierStatusTable array"
727	DEFVAL  { 1 }
728	::= { rectifierStatus 1 }
729
730rectifierStatusTable  OBJECT-TYPE
731	SYNTAX SEQUENCE OF RectifierStatusEntry
732	MAX-ACCESS not-accessible
733	STATUS     current
734	DESCRIPTION
735		"A table listing up to sixteen sequential recifiers, starting
736		from the rectifier number specified by rectifierStatusNoIndex"
737	::= { rectifierStatus 2 }
738
739rectifierStatusEntry  OBJECT-TYPE
740	SYNTAX 	RectifierStatusEntry
741	MAX-ACCESS not-accessible
742	STATUS     current
743	DESCRIPTION
744		"A row of rectifier status data corresponding to the rectifierStatusNoIndex value"
745	INDEX { rectifierStatusID }
746	::= { rectifierStatusTable 1 }
747
748RectifierStatusEntry ::= SEQUENCE {
749	rectifierStatusID
750		Integer32,
751	rectifierStatusStatus
752		INTEGER,
753	rectifierStatusOutputCurrent
754		Integer32,
755	rectifierStatusOutputVoltage
756		Integer32,
757	rectifierStatusTemp
758		Integer32,
759	rectifierStatusType
760		DisplayString,
761	rectifierStatusSKU
762		DisplayString,
763	rectifierStatusSerialNo
764		DisplayString,
765	rectifierStatusRevisionLevel
766		DisplayString
767}
768
769rectifierStatusID  OBJECT-TYPE
770	SYNTAX     Integer32 (1..100)
771	MAX-ACCESS read-only
772	STATUS     current
773	DESCRIPTION
774		"The rectifier ID number of the rectifier record."
775	::= { rectifierStatusEntry 1 }
776
777rectifierStatusStatus  OBJECT-TYPE
778	SYNTAX     INTEGER {
779		absent (0),
780		active (1),
781		failed (2),
782		walkin (3),
783		disabledbycommand (4)
784	}
785	MAX-ACCESS read-only
786	STATUS     current
787	DESCRIPTION
788		"The operational status of the rectifier record.
789		absent (0),
790		active (1),
791		failed (2),
792		walkin (3),
793		disabledbycommand (4)
794
795		"
796	::= { rectifierStatusEntry 2 }
797
798rectifierStatusOutputCurrent  OBJECT-TYPE
799	SYNTAX     Integer32 (0..65535)
800	UNITS 	"1/10 Amperes; i.e. 200 = 20 Amperes"
801	MAX-ACCESS read-only
802	STATUS     current
803	DESCRIPTION
804		"The rectifier current of the rectifier record."
805	::= { rectifierStatusEntry 3 }
806
807rectifierStatusOutputVoltage  OBJECT-TYPE
808	SYNTAX     Integer32 (0..65535)
809	UNITS 	"1/100 Volt; i.e. 5400 = 54.00V"
810	MAX-ACCESS read-only
811	STATUS     current
812	DESCRIPTION
813		"The rectifier voltage of the rectifier record."
814	::= { rectifierStatusEntry 4 }
815
816rectifierStatusTemp  OBJECT-TYPE
817	SYNTAX     Integer32 (0..65535)
818	UNITS 	"Deg. C/10; i.e. 350 = 35.0 Deg. C"
819	MAX-ACCESS read-only
820	STATUS     current
821	DESCRIPTION
822		"The heatsink temperature of the rectifier record."
823	::= { rectifierStatusEntry 5 }
824
825rectifierStatusType  OBJECT-TYPE
826	SYNTAX     DisplayString (SIZE(0..16))
827	MAX-ACCESS read-only
828	STATUS     current
829	DESCRIPTION
830		"The rectifier article number string of the rectifier record."
831	::= { rectifierStatusEntry 6 }
832
833rectifierStatusSKU  OBJECT-TYPE
834	SYNTAX     DisplayString (SIZE(0..16))
835	MAX-ACCESS read-only
836	STATUS     current
837	DESCRIPTION
838		"The rectifier Stock Keeping Unit number or other user-defined ID of the rectifier record."
839	::= { rectifierStatusEntry 7 }
840
841rectifierStatusSerialNo  OBJECT-TYPE
842	SYNTAX     DisplayString (SIZE(0..16))
843	MAX-ACCESS read-only
844	STATUS     current
845	DESCRIPTION
846		"The rectifier serial number string of the rectifier record."
847	::= { rectifierStatusEntry 8 }
848
849rectifierStatusRevisionLevel  OBJECT-TYPE
850	SYNTAX     DisplayString (SIZE(0..16))
851	MAX-ACCESS read-only
852	STATUS     current
853	DESCRIPTION
854		"The rectifier version number string of the rectifier record."
855	::= { rectifierStatusEntry 9 }
856
857acVoltage1  OBJECT-TYPE
858	SYNTAX     Integer32
859	UNITS 	"Volts AC"
860	MAX-ACCESS read-only
861	STATUS     current
862	DESCRIPTION
863		"The AC Voltage of phase 1"
864	::= { acDistribution 1 }
865
866acVoltage2  OBJECT-TYPE
867	SYNTAX     Integer32
868	UNITS 	"Volts AC"
869	MAX-ACCESS read-only
870	STATUS     current
871	DESCRIPTION
872		"The AC Voltage of phase 2"
873	::= { acDistribution 2 }
874
875acVoltage3  OBJECT-TYPE
876	SYNTAX     Integer32
877	UNITS 	"Volts AC"
878	MAX-ACCESS read-only
879	STATUS     current
880	DESCRIPTION
881		"The AC Voltage of phase 3"
882	::= { acDistribution 3 }
883
884alarmMajorHighBattVolt OBJECT-TYPE
885	SYNTAX     INTEGER {
886		normal (0),
887		alarm (1)
888	}
889	MAX-ACCESS read-only
890	STATUS     current
891	DESCRIPTION
892		"The Very High Battery Voltage Alarm"
893	::= { alarmWellknownAlarms 1 }
894
895alarmMinorHighBattVolt OBJECT-TYPE
896	SYNTAX     INTEGER {
897		normal (0),
898		alarm (1)
899	}
900	MAX-ACCESS read-only
901	STATUS     current
902	DESCRIPTION
903		"The High Battery Voltage alarm"
904	::= { alarmWellknownAlarms 2 }
905
906alarmMajorLowBattVolt OBJECT-TYPE
907	SYNTAX     INTEGER {
908		normal (0),
909		alarm (1)
910	}
911	MAX-ACCESS read-only
912	STATUS     current
913	DESCRIPTION
914		"The Very Low Battery Voltage Alarm"
915	::= { alarmWellknownAlarms 3 }
916
917alarmMinorLowBattVolt OBJECT-TYPE
918	SYNTAX     INTEGER {
919		normal (0),
920		alarm (1)
921	}
922	MAX-ACCESS read-only
923	STATUS     current
924	DESCRIPTION
925		"The Low Battery Voltage Alarm"
926	::= { alarmWellknownAlarms 4 }
927
928alarmMajorBatteryHighTemp OBJECT-TYPE
929	SYNTAX     INTEGER {
930		normal (0),
931		alarm (1)
932	}
933	MAX-ACCESS read-only
934	STATUS     current
935	DESCRIPTION
936		"Temperature much too high alarm, or  temperature compensation circuit / probe failure alarm"
937	::= { alarmWellknownAlarms 5 }
938
939alarmMinorBatteryHighTemp OBJECT-TYPE
940	SYNTAX     INTEGER {
941		normal (0),
942		alarm (1)
943	}
944	MAX-ACCESS read-only
945	STATUS     current
946	DESCRIPTION
947		"Temperature much too high alarm"
948	::= { alarmWellknownAlarms 6 }
949
950alarmBatteryDisconnectOpen OBJECT-TYPE
951	SYNTAX     INTEGER {
952		normal (0),
953		alarm (1)
954	}
955	MAX-ACCESS read-only
956	STATUS     current
957	DESCRIPTION
958		"The Battery Disconnect Contactor alarm"
959	::= { alarmWellknownAlarms 7 }
960
961alarmLVD1open OBJECT-TYPE
962	SYNTAX     INTEGER {
963		normal (0),
964		alarm (1)
965	}
966	MAX-ACCESS read-only
967	STATUS     current
968	DESCRIPTION
969		"The A Bus (primary loads) Contactor alarm. The contactor dropout voltage has been
970		 reached and the contactor will release."
971	::= { alarmWellknownAlarms 8 }
972
973alarmLVD2open OBJECT-TYPE
974	SYNTAX     INTEGER {
975		normal (0),
976		alarm (1)
977	}
978	MAX-ACCESS read-only
979	STATUS     current
980	DESCRIPTION
981		"The B Bus (secondary loads) Contactor alarm. The contactor dropout voltage has been
982		 reached and the contactor will release."
983	::= { alarmWellknownAlarms 9 }
984
985alarmLVD3open OBJECT-TYPE
986	SYNTAX     INTEGER {
987		normal (0),
988		alarm (1)
989	}
990	MAX-ACCESS read-only
991	STATUS     current
992	DESCRIPTION
993		"The C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been
994		 reached and the contactor will release.
995		"
996	::= { alarmWellknownAlarms 10 }
997
998alarmACmains OBJECT-TYPE
999	SYNTAX     INTEGER {
1000		normal (0),
1001		alarm (1)
1002	}
1003	MAX-ACCESS read-only
1004	STATUS     current
1005	DESCRIPTION
1006		"The AC voltage has dropped below critical level,
1007		or one or more AC input phases was lost."
1008	::= { alarmWellknownAlarms 11 }
1009
1010alarmBatteryBreakerOpen OBJECT-TYPE
1011	SYNTAX     INTEGER {
1012		normal (0),
1013		alarm (1)
1014	}
1015	MAX-ACCESS read-only
1016	STATUS     current
1017	DESCRIPTION
1018		"Battery string disconnect breaker/fuse alarm"
1019	::= { alarmWellknownAlarms 12 }
1020
1021alarmDistributionBreakerOpen OBJECT-TYPE
1022	SYNTAX     INTEGER {
1023		normal (0),
1024		alarm (1)
1025	}
1026	MAX-ACCESS read-only
1027	STATUS     current
1028	DESCRIPTION
1029		"The Load Distribution breaker/fuse alarm "
1030	::= { alarmWellknownAlarms 13 }
1031
1032alarmMajorRectifier OBJECT-TYPE
1033	SYNTAX     INTEGER {
1034		normal (0),
1035		alarm (1)
1036	}
1037	MAX-ACCESS read-only
1038	STATUS     current
1039	DESCRIPTION
1040		"This is a 'multiple rectifiers have failed' alarm"
1041	::= { alarmWellknownAlarms 14 }
1042
1043alarmMinorRectifier OBJECT-TYPE
1044	SYNTAX     INTEGER {
1045		normal (0),
1046		alarm (1)
1047	}
1048	MAX-ACCESS read-only
1049	STATUS     current
1050	DESCRIPTION
1051		"This is a 'one rectifier has failed' alarm"
1052	::= { alarmWellknownAlarms 15 }
1053
1054alarmMajorBatteryMidpoint OBJECT-TYPE
1055	SYNTAX     INTEGER {
1056		normal (0),
1057		alarm (1)
1058	}
1059	MAX-ACCESS read-only
1060	STATUS     current
1061	DESCRIPTION
1062		"Battery Symmetry (midpoint) Delta Voltage is badly out of limits alarm"
1063	::= { alarmWellknownAlarms 16 }
1064
1065alarmMinorBatteryMidpoint OBJECT-TYPE
1066	SYNTAX     INTEGER {
1067		normal (0),
1068		alarm (1)
1069	}
1070	MAX-ACCESS read-only
1071	STATUS     current
1072	DESCRIPTION
1073		"Battery Symmetry (midpoint) Delta Voltage out of limits alarm"
1074	::= { alarmWellknownAlarms 17 }
1075
1076alarmBatteryLifeEnded OBJECT-TYPE
1077	SYNTAX     INTEGER {
1078		normal (0),
1079		alarm (1)
1080	}
1081	MAX-ACCESS read-only
1082	STATUS     current
1083	DESCRIPTION
1084		"The battery capacity has dropped below critical level.
1085		A battery test has measured the fully charged capacity to be too low,
1086		and thus probably the battery lifecycle to be near expired."
1087	::= { alarmWellknownAlarms 18 }
1088
1089alarmBatteryTestmodeEntered OBJECT-TYPE
1090	SYNTAX     INTEGER {
1091		normal (0),
1092		alarm (1)
1093	}
1094	MAX-ACCESS read-only
1095	STATUS     current
1096	DESCRIPTION
1097		"The system has lowered the battery charge voltage in order to discharge the batteries
1098		to a predefinend level. When the criteria for stopping the battery testing is reached, the
1099		charge voltage is increased to commence normal charging."
1100	::= { alarmWellknownAlarms 19 }
1101
1102alarmBatteryBoostmodeEntered OBJECT-TYPE
1103	SYNTAX     INTEGER {
1104		normal (0),
1105		alarm (1)
1106	}
1107	MAX-ACCESS read-only
1108	STATUS     current
1109	DESCRIPTION
1110		"The system has increased the battery charge voltage in order to equalize the
1111		battery cells charging. When the criteria for stopping the battery equalizing is reached,
1112		the charge voltage is lowered to commence normal charging."
1113	::= { alarmWellknownAlarms 20 }
1114
1115alarmUserConfigurable1 OBJECT-TYPE
1116	SYNTAX     INTEGER {
1117		normal (0),
1118		alarm (1)
1119	}
1120	MAX-ACCESS read-only
1121	STATUS     current
1122	DESCRIPTION
1123		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1124		User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. "
1125	::= { alarmWellknownAlarms 21 }
1126
1127alarmUserConfigurable2 OBJECT-TYPE
1128	SYNTAX     INTEGER {
1129		normal (0),
1130		alarm (1)
1131	}
1132	MAX-ACCESS read-only
1133	STATUS     current
1134	DESCRIPTION
1135		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1136		User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. "
1137	::= { alarmWellknownAlarms 22 }
1138
1139alarmUserConfigurable3 OBJECT-TYPE
1140	SYNTAX     INTEGER {
1141		normal (0),
1142		alarm (1)
1143	}
1144	MAX-ACCESS read-only
1145	STATUS     current
1146	DESCRIPTION
1147		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1148		User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. "
1149	::= { alarmWellknownAlarms 23 }
1150
1151alarmUserConfigurable4 OBJECT-TYPE
1152	SYNTAX     INTEGER {
1153		normal (0),
1154		alarm (1)
1155	}
1156	MAX-ACCESS read-only
1157	STATUS     current
1158	DESCRIPTION
1159		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1160		User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. "
1161	::= { alarmWellknownAlarms 24 }
1162
1163alarmUserConfigurable5 OBJECT-TYPE
1164	SYNTAX     INTEGER {
1165		normal (0),
1166		alarm (1)
1167	}
1168	MAX-ACCESS read-only
1169	STATUS     current
1170	DESCRIPTION
1171		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1172		User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. "
1173	::= { alarmWellknownAlarms 25 }
1174
1175alarmUserConfigurable6 OBJECT-TYPE
1176	SYNTAX     INTEGER {
1177		normal (0),
1178		alarm (1)
1179	}
1180	MAX-ACCESS read-only
1181	STATUS     current
1182	DESCRIPTION
1183		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1184		User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. "
1185	::= { alarmWellknownAlarms 26 }
1186
1187alarmUserConfigurable7 OBJECT-TYPE
1188	SYNTAX     INTEGER {
1189		normal (0),
1190		alarm (1)
1191	}
1192	MAX-ACCESS read-only
1193	STATUS     current
1194	DESCRIPTION
1195		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1196		User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. "
1197	::= { alarmWellknownAlarms 27 }
1198
1199alarmUserConfigurable8 OBJECT-TYPE
1200	SYNTAX     INTEGER {
1201		normal (0),
1202		alarm (1)
1203	}
1204	MAX-ACCESS read-only
1205	STATUS     current
1206	DESCRIPTION
1207		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1208		User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. "
1209	::= { alarmWellknownAlarms 28 }
1210
1211alarmUserConfigurable9 OBJECT-TYPE
1212	SYNTAX     INTEGER {
1213		normal (0),
1214		alarm (1)
1215	}
1216	MAX-ACCESS read-only
1217	STATUS     current
1218	DESCRIPTION
1219		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1220		User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. "
1221	::= { alarmWellknownAlarms 29 }
1222
1223alarmUserConfigurable10 OBJECT-TYPE
1224	SYNTAX     INTEGER {
1225		normal (0),
1226		alarm (1)
1227	}
1228	MAX-ACCESS read-only
1229	STATUS     current
1230	DESCRIPTION
1231		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1232		User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. "
1233	::= { alarmWellknownAlarms 30 }
1234
1235alarmUserConfigurable11 OBJECT-TYPE
1236	SYNTAX     INTEGER {
1237		normal (0),
1238		alarm (1)
1239	}
1240	MAX-ACCESS read-only
1241	STATUS     current
1242	DESCRIPTION
1243		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1244		User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. "
1245	::= { alarmWellknownAlarms 31 }
1246
1247alarmUserConfigurable12 OBJECT-TYPE
1248	SYNTAX     INTEGER {
1249		normal (0),
1250		alarm (1)
1251	}
1252	MAX-ACCESS read-only
1253	STATUS     current
1254	DESCRIPTION
1255		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1256		User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. "
1257	::= { alarmWellknownAlarms 32 }
1258
1259alarmUserConfigurable13 OBJECT-TYPE
1260	SYNTAX     INTEGER {
1261		normal (0),
1262		alarm (1)
1263	}
1264	MAX-ACCESS read-only
1265	STATUS     current
1266	DESCRIPTION
1267		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1268		User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. "
1269	::= { alarmWellknownAlarms 33 }
1270
1271alarmUserConfigurable14 OBJECT-TYPE
1272	SYNTAX     INTEGER {
1273		normal (0),
1274		alarm (1)
1275	}
1276	MAX-ACCESS read-only
1277	STATUS     current
1278	DESCRIPTION
1279		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1280		User configurable alarms will on some systems have text attached to the traps that explains the purpose of the alarm. "
1281	::= { alarmWellknownAlarms 34 }
1282
1283dcSystemTraps  NOTIFICATION-GROUP
1284	NOTIFICATIONS { alarmMajorHighBattVoltTrap,
1285		alarmMinorHighBattVoltTrap,
1286		alarmMajorLowBattVoltTrap,
1287		alarmMinorLowBattVoltTrap,
1288		alarmMajorBatteryHighTempTrap,
1289		alarmMinorBatteryHighTempTrap,
1290		alarmBatteryDisconnectOpenTrap,
1291		alarmLVD1openTrap,
1292		alarmLVD2openTrap,
1293		alarmLVD3openTrap,
1294		alarmACmainsTrap,
1295		alarmBatteryBreakerOpenTrap,
1296		alarmDistributionBreakerOpenTrap,
1297		alarmMajorRectifierTrap,
1298		alarmMinorRectifierTrap,
1299		alarmMajorBatteryMidpointTrap,
1300		alarmMinorBatteryMidpointTrap,
1301		alarmBatteryLifeEndedTrap,
1302		alarmBatteryTestmodeEnteredTrap,
1303		alarmBatteryBoostmodeEnteredTrap,
1304		alarmUserConfigurable1Trap,
1305		alarmUserConfigurable2Trap,
1306		alarmUserConfigurable3Trap,
1307		alarmUserConfigurable4Trap,
1308		alarmUserConfigurable5Trap,
1309		alarmUserConfigurable6Trap,
1310		alarmUserConfigurable7Trap,
1311		alarmUserConfigurable8Trap,
1312		alarmUserConfigurable9Trap,
1313		alarmUserConfigurable10Trap,
1314		alarmUserConfigurable11Trap,
1315		alarmUserConfigurable12Trap,
1316		alarmUserConfigurable13Trap,
1317		alarmUserConfigurable14Trap }
1318	STATUS     current
1319	DESCRIPTION
1320		" This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs.
1321		 Each alarm condition is represented by a Alarm Condition Trap and an associated OFF
1322		 Trap, which is optionally transmitted according to the state of  OID systemSendOffTrap"
1323	::= { eltekPlant 8 }
1324
1325
1326
1327
1328
1329alarmMajorHighBattVoltTrap  NOTIFICATION-TYPE
1330	OBJECTS { alarmMajorHighBattVolt}
1331	STATUS     current
1332	DESCRIPTION
1333		"The Very High Battery Voltage alarm"
1334	::= { dcSystemTraps 1 }
1335
1336alarmMinorHighBattVoltTrap  NOTIFICATION-TYPE
1337	OBJECTS { alarmMinorHighBattVolt}
1338	STATUS     current
1339	DESCRIPTION
1340		"The High Battery Voltage alarm"
1341	::= { dcSystemTraps 2 }
1342
1343alarmMajorLowBattVoltTrap  NOTIFICATION-TYPE
1344	OBJECTS { alarmMajorLowBattVolt}
1345	STATUS     current
1346	DESCRIPTION
1347		"The Very Low Battery Voltage Alarm"
1348	::= { dcSystemTraps 3 }
1349
1350alarmMinorLowBattVoltTrap  NOTIFICATION-TYPE
1351	OBJECTS { alarmMinorLowBattVolt}
1352	STATUS     current
1353	DESCRIPTION
1354		"The Low Battery Voltage Alarm"
1355	::= { dcSystemTraps 4 }
1356
1357alarmMajorBatteryHighTempTrap  NOTIFICATION-TYPE
1358	OBJECTS { alarmMajorBatteryHighTemp}
1359	STATUS     current
1360	DESCRIPTION
1361		"High Battery temperature alarm or
1362		Temperature Compensation circuit / probe failure alarm"
1363	::= { dcSystemTraps 5 }
1364
1365alarmMinorBatteryHighTempTrap  NOTIFICATION-TYPE
1366	OBJECTS { alarmMinorBatteryHighTemp}
1367	STATUS     current
1368	DESCRIPTION
1369		"High Battery temperature alarm"
1370	::= { dcSystemTraps 6 }
1371
1372alarmBatteryDisconnectOpenTrap  NOTIFICATION-TYPE
1373	OBJECTS { alarmBatteryDisconnectOpen}
1374	STATUS     current
1375	DESCRIPTION
1376		"The Battery Disconnect Contactor alarm"
1377	::= { dcSystemTraps 7 }
1378
1379alarmLVD1openTrap  NOTIFICATION-TYPE
1380	OBJECTS { alarmLVD1open}
1381	STATUS     current
1382	DESCRIPTION
1383		"The A Bus (primary loads) Contactor is open alarm"
1384	::= { dcSystemTraps 8 }
1385
1386alarmLVD2openTrap  NOTIFICATION-TYPE
1387	OBJECTS { alarmLVD2open}
1388	STATUS     current
1389	DESCRIPTION
1390		"The B Bus (secondary loads) Contactor is open alarm"
1391	::= { dcSystemTraps 9 }
1392
1393alarmLVD3openTrap  NOTIFICATION-TYPE
1394	OBJECTS { alarmLVD3open}
1395	STATUS     current
1396	DESCRIPTION
1397		"The C Bus (critical loads) Contactor alarm. The contactor dropout voltage has been
1398		 reached and the contactor is released.
1399		"
1400	::= { dcSystemTraps 10 }
1401
1402alarmACmainsTrap  NOTIFICATION-TYPE
1403	OBJECTS { alarmACmains}
1404	STATUS     current
1405	DESCRIPTION
1406		"The AC voltage has dropped below critical level,
1407		or one or more AC input phases was lost."
1408	::= { dcSystemTraps 11 }
1409
1410alarmBatteryBreakerOpenTrap  NOTIFICATION-TYPE
1411	OBJECTS { alarmBatteryBreakerOpen}
1412	STATUS     current
1413	DESCRIPTION
1414		"Battery string disconnect breaker/fuse alarm"
1415	::= { dcSystemTraps 12 }
1416
1417alarmDistributionBreakerOpenTrap  NOTIFICATION-TYPE
1418	OBJECTS { alarmDistributionBreakerOpen}
1419	STATUS     current
1420	DESCRIPTION
1421		"The Load Distribution breaker/fuse alarm"
1422	::= { dcSystemTraps 13 }
1423
1424alarmMajorRectifierTrap  NOTIFICATION-TYPE
1425	OBJECTS { alarmMajorRectifier}
1426	STATUS     current
1427	DESCRIPTION
1428		"This is a 'multiple rectifiers have failed' alarm"
1429	::= { dcSystemTraps 14 }
1430
1431alarmMinorRectifierTrap  NOTIFICATION-TYPE
1432	OBJECTS { alarmMinorRectifier}
1433	STATUS     current
1434	DESCRIPTION
1435		"This is a 'one rectifier has failed' alarm"
1436	::= { dcSystemTraps 15 }
1437
1438alarmMajorBatteryMidpointTrap  NOTIFICATION-TYPE
1439	OBJECTS { alarmMajorBatteryMidpoint}
1440	STATUS     current
1441	DESCRIPTION
1442		"Battery Symmetry (midpoint) Delta Voltage out of 'major fault' limits alarm"
1443	::= { dcSystemTraps 16 }
1444
1445alarmMinorBatteryMidpointTrap  NOTIFICATION-TYPE
1446	OBJECTS { alarmMinorBatteryMidpoint}
1447	STATUS     current
1448	DESCRIPTION
1449		"Battery Symmetry (midpoint) Delta Voltage out of limits alarm"
1450	::= { dcSystemTraps 17 }
1451
1452alarmBatteryLifeEndedTrap  NOTIFICATION-TYPE
1453	OBJECTS { alarmBatteryLifeEnded}
1454	STATUS     current
1455	DESCRIPTION
1456		"The battery capacity has dropped below critical level.
1457		A battery test has measured the fully charged capacity to be too low,
1458		and thus probably the battery lifecycle to be near expired."
1459	::= { dcSystemTraps 18 }
1460
1461alarmBatteryTestmodeEnteredTrap  NOTIFICATION-TYPE
1462	OBJECTS { alarmBatteryTestmodeEntered}
1463	STATUS     current
1464	DESCRIPTION
1465		"The system has lowered the battery charge voltage in order to discharge the batteries
1466		to a predefinend level. When the criteria for stopping the battery testing is reached, the
1467		charge voltage is increased to commence normal charging."
1468	::= { dcSystemTraps 19 }
1469
1470alarmBatteryBoostmodeEnteredTrap  NOTIFICATION-TYPE
1471	OBJECTS { alarmBatteryBoostmodeEntered}
1472	STATUS     current
1473	DESCRIPTION
1474		"The system has increased the battery charge voltage in order to equalize the
1475		battery cells charging. When the criteria for stopping the battery equalizing is reached,
1476		the charge voltage is lowered to commence normal charging."
1477	::= { dcSystemTraps 20 }
1478
1479alarmUserConfigurable1Trap  NOTIFICATION-TYPE
1480	OBJECTS { alarmUserConfigurable1}
1481	STATUS     current
1482	DESCRIPTION
1483		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1484		User configurable alarms will on some systems have text attached to the traps
1485		that explains the purpose of the alarm. "
1486	::= { dcSystemTraps 21 }
1487
1488alarmUserConfigurable2Trap  NOTIFICATION-TYPE
1489	OBJECTS { alarmUserConfigurable2}
1490	STATUS     current
1491	DESCRIPTION
1492		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1493		User configurable alarms will on some systems have text attached to the traps
1494		that explains the purpose of the alarm. "
1495	::= { dcSystemTraps 22 }
1496
1497alarmUserConfigurable3Trap  NOTIFICATION-TYPE
1498	OBJECTS { alarmUserConfigurable3}
1499	STATUS     current
1500	DESCRIPTION
1501		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1502		User configurable alarms will on some systems have text attached to the traps
1503		that explains the purpose of the alarm. "
1504	::= { dcSystemTraps 23 }
1505
1506alarmUserConfigurable4Trap  NOTIFICATION-TYPE
1507	OBJECTS { alarmUserConfigurable4}
1508	STATUS     current
1509	DESCRIPTION
1510		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1511		User configurable alarms will on some systems have text attached to the traps
1512		that explains the purpose of the alarm. "
1513	::= { dcSystemTraps 24 }
1514
1515alarmUserConfigurable5Trap  NOTIFICATION-TYPE
1516	OBJECTS { alarmUserConfigurable5}
1517	STATUS     current
1518	DESCRIPTION
1519		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1520		User configurable alarms will on some systems have text attached to the traps
1521		that explains the purpose of the alarm. "
1522	::= { dcSystemTraps 25 }
1523
1524alarmUserConfigurable6Trap  NOTIFICATION-TYPE
1525	OBJECTS { alarmUserConfigurable6}
1526	STATUS     current
1527	DESCRIPTION
1528		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1529		User configurable alarms will on some systems have text attached to the traps
1530		that explains the purpose of the alarm. "
1531	::= { dcSystemTraps 26 }
1532
1533alarmUserConfigurable7Trap  NOTIFICATION-TYPE
1534	OBJECTS { alarmUserConfigurable7}
1535	STATUS     current
1536	DESCRIPTION
1537		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1538		User configurable alarms will on some systems have text attached to the traps
1539		that explains the purpose of the alarm. "
1540	::= { dcSystemTraps 27 }
1541
1542alarmUserConfigurable8Trap  NOTIFICATION-TYPE
1543	OBJECTS { alarmUserConfigurable8}
1544	STATUS     current
1545	DESCRIPTION
1546		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1547		User configurable alarms will on some systems have text attached to the traps
1548		that explains the purpose of the alarm. "
1549	::= { dcSystemTraps 28 }
1550
1551alarmUserConfigurable9Trap  NOTIFICATION-TYPE
1552	OBJECTS { alarmUserConfigurable9}
1553	STATUS     current
1554	DESCRIPTION
1555		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1556		User configurable alarms will on some systems have text attached to the traps
1557		that explains the purpose of the alarm. "
1558	::= { dcSystemTraps 29 }
1559
1560alarmUserConfigurable10Trap  NOTIFICATION-TYPE
1561	OBJECTS { alarmUserConfigurable10}
1562	STATUS     current
1563	DESCRIPTION
1564		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1565		User configurable alarms will on some systems have text attached to the traps
1566		that explains the purpose of the alarm. "
1567	::= { dcSystemTraps 30 }
1568
1569alarmUserConfigurable11Trap  NOTIFICATION-TYPE
1570	OBJECTS { alarmUserConfigurable11}
1571	STATUS     current
1572	DESCRIPTION
1573		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1574		User configurable alarms will on some systems have text attached to the traps
1575		that explains the purpose of the alarm. "
1576	::= { dcSystemTraps 31 }
1577
1578alarmUserConfigurable12Trap  NOTIFICATION-TYPE
1579	OBJECTS { alarmUserConfigurable12}
1580	STATUS     current
1581	DESCRIPTION
1582		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1583		User configurable alarms will on some systems have text attached to the traps
1584		that explains the purpose of the alarm. "
1585	::= { dcSystemTraps 32 }
1586
1587alarmUserConfigurable13Trap  NOTIFICATION-TYPE
1588	OBJECTS { alarmUserConfigurable13}
1589	STATUS     current
1590	DESCRIPTION
1591		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1592		User configurable alarms will on some systems have text attached to the traps
1593		that explains the purpose of the alarm. "
1594	::= { dcSystemTraps 33 }
1595
1596alarmUserConfigurable14Trap  NOTIFICATION-TYPE
1597	OBJECTS { alarmUserConfigurable14}
1598	STATUS     current
1599	DESCRIPTION
1600		"Generic alarm linked to user specified alarms. These have no specific name in the MIB.
1601		User configurable alarms will on some systems have text attached to the traps
1602		that explains the purpose of the alarm. "
1603	::= { dcSystemTraps 34 }
1604
1605
1606
1607
1608END
1609
1610
1611-- This MIB was created using NuDesign Team's Visual MIBuilder (Ver 4.4).
1612
1613